5
GG-6
Installation
Locating the GG-6
The important consideration when installing GG-6 control panel is that it
must be easily accessible for operating personnel.
Installation Guidelines:
• Mount control panel on a solid surface with minimal vibration.
•
Mount control panel thru the holes in the mounting flanges of the
enclosure.
• Mount control panel in a general-purpose location only. Do not install in a
hazardous environment.
• Mount control panel away from electromagnetic interference.
• Protect control panel from physical damage.
• During installation, cover conduit holes and close the enclosure cover to
prevent debris from falling into the equipment.
• If mounting on a wall with studs, the mounting screws should be screwed
into the studs.
GG-XM Installation
For GG-XM expansion module installations, mount the units inline from left
to right, as shown in the drawing below.
Maximum mounting distance between enclosures is approximately 10
inches. If mounting space does not allow for inline installation due to
space restrictions, contact Calibration Technologies for an extended length
interconnect cable and recommendations.
If using conduit, be sure to use ¾” conduit for GG-XM interconnects to allow
room for cable harness plugs.
See system wiring diagram on page 8 for more details.