16
GG-6
4) Configure Relay
The default setting for all relays is non-fail safe
mode. Setting the relay to fail safe mode allows
the relay to be energized during normal operation.
Loss of power or an action event targeting this
relay will cause the relay to change states. See
Relay Wiring section for more details. Use YES
or NO keys to set fail safe mode. Press ENTER
and use alphanumeric keys to enter relay name.
Assigning a relay name during the installation
provides an at-a-glance relay assignment in the
configuration menu, without the need for electrical
drawings lookup.
5) Configure System
The GG-6 is equipped to accommodate both local
and remote mounted reset and silence switches
to comply with regulatory codes. For information
about remote mounted switches, contact CTI.
Default settings for reset and silence are LOCAL.
Press ENTER and use the up or down arrow keys
to select LOCAL, REMOTE or BOTH. Use the up or
down arrows to enter the number of Expansion
Modules used for the control panel.
6) Configure MODBUS
The GG-6 is equipped to accommodate the
GG-RD1 remote display module. The default
settings shown will work with the defualt settings
of the GG-RD1. Contact CTI for further help with
MODBUS configurations
Clock
Set current time and date. Press ENTER and use
alphanumeric keys to set time and date. Date is 24
hour military format.
Contrast
Adjust contrast to allow for best viewing of LCD.
Press ENTER and use alphanumeric keys to set
desired contrast.
Relay Test
The relay test menu allows the relay outputs to be
tested individually for correct output functions.
Press PREV or NEXT keys to select relay to be
tested. Note relay name at bottom of screen.
Press YES to Set the relay. The relay state will
display “Set” and the relay will activate.
Press NO to Clear the relay once the relay output
function has been verified. The relay state will
display “Clear” and the relay will de-activate.
Press PREV or NEXT keys to advance to next relay,
or ESC to return to main menu.
About
Current software version.
This completes the configuration portion of the control panel. ESC back to Config
main menu. Pressing ESC from the Config Menu will display important exit-
options. Caution: Pressing ESC again will exit without saving changes.