53
For the property owner
CTC EcoZenith
I
550
Re-cooling
“Yes” The function means that the system endeavors to reduce the temperature
in the tank to set reference value. This means that the solar collectors are
used as cooling coils for a short period of time.
“No” The re-cooling function is deactivated
Factory value No (setting Yes/No).
Frost protect.
Setting determining if anti-freeze should be activated or not.
Factory value No (setting Yes/No).
Frost protect.°C
Setting of the temperature at which the frost protection function is activated.
Factory value -25°C (setting -30 to -7°C).
Calibration Sensors Menu
(Installer/Settings/Solar/Calibration sensors)
Here the sensor temperatures can be corrected.
From solar pnl °C
Correction of the solar panel’s temperature sensor for outgoing temperature (70)
Factory value 0°C (setting -3 to 3°C).
To solar panel °C
Correction of the solar panel’s temperature sensor for incoming temperature (71)
Factory value 0°C (setting -3 to 3°C).
Charge temp solar °C
Correction of the solar panel’s charge temperature sensor (72).
Used when the type is defined as “Heat exchanger”.
Factory value 0°C (setting -3 to 3°C).
Calibration sensors
From solar pnl°C
0
To solar panel°C
0
Charge solar °C
0