EcoAir 610M / 614M
EcoAir 622M
Pressure differential (kPa)
5.4 Pressure differential diagram for CTC EcoAir 600M
Setting the temperature differential
For external control, a circulation pump is installed so that the right flow
through the heat pump can be guaranteed.
Outdoor temp. (°C)
-10
-5
0
+5
+7
+10
CTC EcoAir 610M / 614M
Primary flow 35 °C Flow = 0.21 l/s
4 °C
4.5 °C
5.5 °C
6.5 °C
7 °C
8 °C
CTC EcoAir 622M
Primary flow 35 °C Flow = 0.39 l/s
4 °C
5 °C
6 °C
6.5 °C
7 °C
8 °C
In some systems the entire radiator flow goes through the heat pump, which
means the pump must be sized according to the flow of the entire system.
For safe operation, the following flows should be considered:
• 760 l/h (CTC EcoAir 610M / 614M)
• 1400 l/h (CTC EcoAir 622M)
This provides a temperature differential of approx. 7 °C for an outside
temperature of +7 °C and a primary flow temperature of 35 °C.
Flow speed Q (l/s)
Set the right temperature differential by adjusting the speed of the circulation
pump. This is to ensure that the right differential for the current outdoor
temperature is produced according to the table.
Summary of Contents for 588400001
Page 2: ......
Page 32: ...32 CTC EcoAir 610M 614M 622M 400 V 3N 6 9 Wiring diagram 400 V 3N A3...
Page 33: ...33 CTC EcoAir 610M 614M 622M 400 V 3N...
Page 34: ...34 CTC EcoAir 610M 614M 622M 400 V 3N 6 10 Wiring diagram 400 V 3N A4...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......