![CSI MST32-S2 Installation & Operation Manual Download Page 12](http://html1.mh-extra.com/html/csi/mst32-s2/mst32-s2_installation-and-operation-manual_2692688012.webp)
12
Main Menu
12
:
00
1.
To enter Main Menu, press the
Menu/Enter
button.
(Time of Day will flash)
2.
To set the
Time of Day
, press the
Set/Change
button.
(First
digit
will
flash)
Example
[
12-00
]
-
To change digit value, press the
Set/Change
button.
-
To accept the digit value, press the
Menu/Enter
button.
-
Next digit will flash to begin setting.
-
Once the last digit display is accepted, all digits will flash.
3.
To set
A.M.
or
P.M
., press the
Menu/Enter
button.
-
To change digit value, press the
Set/Change
button.
Example [
A
]
-
To accept the digit value, press the
Menu/Enter
button.
-
Once A.M. or P.M. is accepted, the next menu item will flash.
4.
To set
Hardness
an “H” will appear to enter Compensated Hardness in grains per gallon (gpg)
Default setting is 25 gpg.
Example [
H - 25
]
5.
To Exit Main Menu, press the
Menu/Enter
button.
Note: If no buttons are pressed for 60 seconds, the Main Menu will be exited automatically.
Normal Operation
1.
Home Display
Metered
models alternate the Time of Day and Gallons left until the next regeneration. The meter will count
down to zero (0000) and then regenerate at the scheduled time set.
2.
Battery Back-Up
(Uses a standard 9-volt alkaline battery.)
Features of Battery Back-Up:
• During power failures, the battery will maintain the time of day as long as the battery has power. The
display is turned off to conserve battery power during this time. To confirm that the battery is working,
press either button and the display will turn on for five (5) seconds.
• If power failure occurs while system is regenerating, the Signature 2 will motor to a shut off position
to prevent constant flow to drain. Depending upon system pressure and other factors, it is possible to
observe a reduced flow to drain during this step. After power is restored, the Signature 2 will return
and finish the cycle where it left off prior to the power interruption.
• When used without battery back-up, during a power failure, the unit stops at its current point in the
regeneration position and then restarts at that point when the power is restored. The time will be
offset by the increment of time the unit was
without power, so it is necessary to reset the time of day
on the unit. No other system will be affected.
Programming the Control Valve