MR-AHU

 

2

Installation Sheet (TCON154 11/97)

 

I/STAT, S/STAT and W/STAT Connections

 

1.

 

Connect the I/STAT, S/STAT, or W/STAT white, red, and 
black conductors to TB3 – 1 through TB3 – 3 (Signal, Power, 
and Ground) as shown in 

Figure4, “I/STAT and S/STAT 

Connection”

.

 

2.

 

When connecting an S/STAT connect the blue and yellow 
conductors to TB4 – 4 (Input 4). Refer to 

Table 2

, “DIP 

Switch Configuration Settings”.

 

Connecting the Sub-LAN

 

1.

 

Connect the + lead of the twisted pair sub-LAN cable to 
terminal TB2 – 1 (LAN+, see 

Figure5, “Sub-LAN 

Connections”

).

 

2.

 

Connect the – lead of the twisted pair sub-LAN cable to 
terminal TB2 – 2 (LAN –).

 

3.

 

Shield drain wire continuity must be maintained as the sub-
LAN cable passes through each MR-AHU. Shield drain 
wires from each controller sub-LAN cable must be twisted 
together, insulated, and tied back such that wires do not 
come in contact with ground or any conductive surface.

 

4.

 

Connect the shield drain wire directly to Electrical Service 
Earth Ground at only one end of the cable (e.g., at the MCI, 
MRI, or at one MR-AHU).

 

Note:

 

Refer to “Cable Requirements” in 

“Specifications” on 

page 4

.

 

Figure 4.

I/STAT and S/STAT Connection

1

2

3

4

5

6

TB4
INPUTS

SENSOR

TB3

GROUND

+12V

INPUT 4

INPUT 3

INPUT 2

INPUT 1

INPUT PORT

1

2

3

SIGNAL

POWER

GROUND

I/STAT

PORT

White

Red

Black

Blue

Yellow

S/STAT Only

I/STAT, W/STAT and S/STAT

 

Figure 5.

Sub-LAN Connections

LAN

P1

TB1

TB2

AC PWR

12

12

LAN +

LAN

PORT

LAN –

24V ~

GROUND

PWR