TROUBLE-
SHOOTING
Q. WHAT SHOULD I DO WHEN THE CIP 2.0 SYSTEM HANGS ON “WAITING FOR
FACILITY PERMISSION?
Verify whether the circuit needs permission from the plant before starting.
If the circuit does not need permission before starting, have an elevated user
change the configuration type for the circuit under Circuit Configuration.
If the circuit does need permission, verify that you are getting a signal back from
the plant PLC, as the system may be requesting permission and not getting a
response.
Q. WHAT SHOULD I DO IF I ACCIDENTALLY CLOSE THE HMI CLIENT?
A. Locate the shortcut on the Windows Desktop called
TC-CIP .cli
, double click
this file to re-launch the HMI client.
Q. WHAT SHOULD I DO IF I CANNOT MANUALLY RUN THE CIP PUMP?
Verify that there is at least one tank discharge valve open to supply the pump
with liquid.
Verify that there is a tank level over 5% in the tank that is supplying the liquid.
If either of the above is not true there should be a stop sign symbol next to the
pump indicating it cannot run. This is done by design to protect the pump from
running dry.
Q. WHAT SHOULD I DO IF I CANNOT MANUALLY RUN THE HEATER OR STEAM
VALVE?
Verify that there is a recirculation loop established and that the flow is over 10
GPM.
Ensure the steam supply valve status shows in the open position.
If the valve is not in open position, a yellow exclamation point indicates that the
equipment cannot run, to protect the heat exchanger from heating without flow.