Float System Troubleshooting
-The panel power lights are not on. -Make sure the Control / Alarm
breaker(s) are turned on.
-Make sure you have the correct
incoming voltage.
-Make sure all necessary jumper
wires are in the proper terminal.
-Make sure both fuses are not
blown. If both fuses are blown,
the Fuse Trip Indicator Lights will
not operate.
IF
THEN
-Alarm Fuse or Control Fuse light
is on.
-A fuse has blown. Replace the
fuse with a similiar amperage 5
x 20mm fuse. If the new fuse also
blows, check the incoming field
wiring.
Note:
Extra fuses are located on
the back of the subdoor.
-
The Float Indicator Lights are
flashing.
-Make sure all the floats are
connected to the proper terminals.
-Turn the control panel off. Wait 10
seconds then turn the control
panel back on. If a float had been
skipped in the order of operation
this should clear the error.
-If the floats are connected
through a junction box, make sure
there is no water in the junction
box.
-A float may be malfunctioning.
RK Series
™