background image

All installations and services must be performed by qualified service personnel. 

B. DRAFT REGULATORS: 
 
A  draft  regulator  is  supplied  with  the  furnace  and    should  be  installed  according  to  the  regulator  manufacturers 
recommendations. With the burner operating, use a draft gauge to adjust the regulator to the proper setting. (refer to 
the instructions enclosed with draft regulator to adjust to the proper setting). When the burner air supply and draft are 
properly adjusted, the overfire draft should be a negative (-).01" to (-).02" WC

  1

, as measured at the 5/16" overfire 

air tap (See Fig. 4). This tap is provided in the upper burner mounting plate. To measure the flue draft, punch a small 
hole in the vent connector pipe as close to the furnace as possible and always before the draft regulator. 
 

 

 

 

 

 

 

 

 

Note: 

1. Draft overfire may be positive for high fire applications but not to exceed (+).02" WC. 

 
 
C.  DUCT WORK/AIR CONDITIONING: 
 
If the furnace is used in connection with summer air conditioning (cooling), the furnace should be installed parallel 
with  or  on  the  upstream  side  of  the  evaporator  coil  to  avoid  condensation  in  the  furnace  heat  exchanger.  If  the 
cooling unit is installed with a parallel flow arrangement, dampers or other means used to control flow of air should 
be  provided  to  prevent  chilled  air  from  entering  the  furnace.  If  such  a  damper  is  manually  operated,  it  must  be 
equipped with a means to prevent operation of either unit, unless the damper is in the full heat or cool position. 
 
The duct system should again follow the current design standard of Air Conditioning Contractors of America                 
(ACCA) or ASHRAE Fundamentals volume.The most common location for the A-shaped coil (A style) is shown in 
Fig. 1. 

 

Fig 1: Acceptable locations for the air conditioner evaporator coil. 

 

NOTICE:  The  minimum  coil    pan  clearance  for  a  drum  type  heat  exchanger  is  three  inches  unless  specified 
otherwise by the individual coil manufacturer.  
 
 
D.  FILTERS MOUNTED EXTERNAL TO FURNACE 
 
On  highboy  furnaces,  it  is  necessary  to  cut  the  return  air  opening  in  the  side  or  rear  casing,  depending  upon  the 
needs of the specific installation. 
The filter rack provided with the furnace, refer to Fig. 2, will serve as a template to scribe a mark for the return air 
opening  on  the  casing.  Place  the  filter  rack  on  a  side  casing  approximately  one  inch  up  from  the  bottom  of  the 
furnace  and  centered  from  side  to  side.  Place  the  securing  flange  against  the  casing  when  locating  the  return  air 
opening. For your convenience, (4) locator knock-outs have been placed at the proper locations on both the left and 
right side casings. 

 

Summary of Contents for CSHB60-90ABP

Page 1: ...nce Improper installation adjustment alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional information consult a qualified installer or service agency These instructions should be read prior to installing the furnace retained for reference by qualified service personnel reviewed before performing an...

Page 2: ...njury substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWARNING The area around the furnace should be kept free and clear of combustible liquids and material especially papers and rags See Page 9 cWARNING NEVER burn garbage or refuse in your furnace Never ...

Page 3: ...IR CONDITIONING 4 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANING INSTRUCTIONS 8 III USERS INFORMATION SECTION 9 A OIL SUPPLY 9 B COMBUSTION AIR SUPPLY 9 C INSPECTION AREAS 9 D STARTING THE BURNER 9 E FILTER CLEANING AND LOCATIONS 10 APPENDIX A REPLACEMENT PARTS LIST 11 APPENDIX B W...

Page 4: ...protected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MATERIAL COMBUSTIBLE MATERIAL Material made of or surfaced with wood compressed paper plant fibers plastics or other material that will ignite and burn whether flame resistant or not NON COMBUSTIBLE MATERIAL Mater...

Page 5: ...ial oil furnaces If a power venter must be used it is the responsibility of the installer and power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the CSHB60 90 it is possible to rotate the flue elbow which is factory installed for vertical discharge 90 counterclockwise from the vertical position to adapt to various venting systems c CAUTION MUST BE T...

Page 6: ...meter with the included Beckett side wall vent kit The side wall vent may be installed either through the upper knock out on the left side casing of the unit or vertically out the top opening of the vestibule The 4 flexible vent pipe included w Field vent kit is able to be installed at 2 clearance to combustibles The combustion air inlet can be installed through either the lower left side casing k...

Page 7: ...ment dampers or other means used to control flow of air should be provided to prevent chilled air from entering the furnace If such a damper is manually operated it must be equipped with a means to prevent operation of either unit unless the damper is in the full heat or cool position The duct system should again follow the current design standard of Air Conditioning Contractors of America ACCA or...

Page 8: ...rack can be anchored to the furnace with screws or pop rivets through the securing flange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions for adapting the return air plenum to the filter rack are provided See Fig 2 E LIMIT POSITION AND LOCATION cWARNING The predetermined limit location on this Crown oil fired furnace has been tested an...

Page 9: ...s the chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and components in burner mounting plate area Fig 5 Burner insertion illustration Top view When mounting the burner the mounting plate Fig 4 must be removed to provide access to the area in front of the combustion chamber A fiber insul...

Page 10: ...OR SOLID CONE FOR EXAMPLE A NOZZLE RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information contact Crown Boiler Co P O Box 14818 3633 I St Philadelphia PA 19134 All rates shown achieved with 120 PSIG pump pressure for Beckett AFG Based on 2 domestic heating fuel oil having heating va...

Page 11: ... With access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum cleaner to remove any soot build up NOTE A one inch outside diameter vacuum cleaner hose will fit into the radiator To vacuum and brush the outer radiator of the heat exchanger go through the clean out op...

Page 12: ...iscoloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage around seams in pipe indicated by soot or condensate streaks CHIMNEY OR VENTING SYSTEM The furnace venting system should be inspected for signs of rust corrosion pitting or holes and signs of condensa...

Page 13: ...system and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The filter rack will be located between the return air plenum and the return air opening on the side of the furnace refer to figure 8 Slide the dirty filter out clean it with a mild soap and water solution ...

Page 14: ...All installations and services must be performed by qualified service personnel 11 APPENDIX A Replacement Parts List ...

Page 15: ...All installations and services must be performed by qualified service personnel 12 ...

Page 16: ...All installations and services must be performed by qualified service personnel 13 APPENDIX B Wiring Diagrams CSHB60 90ABP BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier ...

Page 17: ...All installations and services must be performed by qualified service personnel 14 CSHB60 90ABT ...

Reviews: