Troubleshooting Chart for CWI Boilers Without Tankless Heaters
Caution
: Read page 33 before attempting to use this chart
Thermostat
calls for heat
Circulator
start?
120 volts
at
L1
&
L2
?
120 volts at
C1
&
C2
?
N
N
*
Power off
*
Blown fuse or
tripped breaker
*
Miswired or
loose electrical
connection in
120V line
Remove t'stat or
zone valve end
switch wires from
T
&
TV
terminals on
L8148E. Install
temporary jumper
across terminals
T
and
TV
.
Does
circulator
run now?
*
Defective
L8148E-see
Note 6 on page
33.
*
Loose connection in t'stat or
zone valve end switch wiring
*
Defective t'stat or zone valve
end switch
*
T'stat or zone system
miswired-consult t'stat or
zone valve manufacturer's
instructions
Vent
damper
open?
24 volts
across
B
and
R
(limit switch) in
L8148E ?
*
Boiler off on
limit
*
Defective
high limit.
24 volts
between pins
1
&
4
(blue&yellow)and
2
&
4
(orange&yellow) on
damper end of damper
harness? See
Note 7 on page 33.
*
Loose
connection
between
damper
harness and
L8148E
*
Defective
damper
harness.
*
Defective
L8148E
*
Obstruction in
path of damper
blade
*
Defective
damper motor
*
Loose
connection
between damper
harness and
damper
Y
START
24 volts
across
T
&
TV
?
120 volts
across
terminals at
circulator?
*
Seized or
defective
circulator
*
Bad electrical
connection
between
C1
or
C2
and
circulator
N
Y
N
Y
N
Y
Y
Y
N
N
Y
N
Y
Y
N
Y
N
Boiler
Equipped
With
Damper?
Summary of Contents for CWI103
Page 2: ......
Page 17: ...15 15 FIGURE 12 INDIRECT WATER HEATER BOILER SIDE PIPING FIGURE 11 STANDARD BOILER PIPING ...
Page 34: ...32 32 Notes ...
Page 41: ...39 39 Notes ...
Page 43: ...41 41 ...
Page 45: ...43 43 ...
Page 47: ...45 45 ...
Page 49: ...47 47 FIGURE A1 BASE HEAT EXCHANGER FLUE COLLECTOR ASSEMBLY ...
Page 51: ...49 49 FIGURE A2 JACKET INSTALLATION ...
Page 53: ...51 51 FIGURE A3 TAPPING LOCATIONS SEE TEXT FOR TAPPING USES ...
Page 54: ...52 52 Notes ...
Page 55: ...53 53 Notes ...