background image

3

Detector placement should be determined following advice of experts

having specialist knowledge of gas dispersion, the plant processing equipment as

well as safety and engineering issues. 

The agreement reached on the

locations of sensors should be recorded

. Crowcon would be pleased to assist

in the selection and siting of gas detectors.

3.2 Mounting

The mounting detail of TXgard-Plus is given in Diagram 1. TXgard-Plus should

be installed at the designated location with the detector pointing down. This

ensures that dust or water will not collect on the sinter and stop gas entering

the detector.

3.3 Cabling Requirement

Cabling to TXgard-Plus must be in accordance with the recognised

standards of the appropriate authority in the country concerned and meet the

electrical requirements of the detector. Crowcon recommend the use of steel

wire armoured (SWA) cable and suitable explosion proof glands must be

used. Alternative cabling techniques, such as steel conduit, may be

acceptable provided appropriate standards are met.

TXgard-Plus requires a dc supply of 10-30 V at up to 100 mA.

Ensure the minimum dc supply of 10 V is observed at the detector, taking into

account the voltage drop due to cable resistance.

For example, a nominal dc supply at the control panel of 24 V has a

guaranteed minimum supply of 18V. The maximum voltage drop 

allowed is therefore 8V. TXgard-Plus can demand up to 100 mA and so the

maximum loop resistance allowed is 80 Ohms. A 1.0 mm

2

cable will typically

allow cable runs up to 2000 m. Table 4 shows maximum cable distances

given typical cable parameters.

CSA

Resistance (Ohms per km)

Max. distance

mm

2

(awg)

Cable

Loop m 

(ft)

1.0 (17)

18.1

36.2

2000 (6560)

1.5 (15)

12.1

24.2

3000 (9840)

Table 4

: Maximum cable distances for typical cables

Acceptable cross sectional area of cable is 0.5 to 1.5 mm

2

. Table 4 provides

guidance only, actual cable parameters for each application should be used to

calculate maximum cable distances.

3.4 Electrical Connections (4-20mA use)

All connections are made via the terminal board mounted in the base of the

junction box (see Diagram 2). The 3 wires from the 96HD are colour coded

and should be terminated in the corresponding colour coded terminal

(terminals 4, 5 & 6). Terminals 1 (0 Vdc), 2 (10-30 Vdc) and 3 (4-20mA signal)

are connected to the control equipment. TXgard-Plus is factory set as a 4-

20 mA source device unless specified otherwise when ordering (see Section

2 to change configuration). Diagram 3 summarises the electrical

connections. 

Note: The junction box and cable armour must be earthed at the

detector and control panel to limit the effect of radio frequency

interference and to maintain electrical safety.

All electrical connections to the optional relays are made via the 6-way

terminal block numbered 7 to 12 on the terminal board in the base of the

junction box (see Diagram 2). The relay contacts are rated 

1 A @ 30 Vdc.

4. OPERATION

WARNING

Prior to carrying out any work ensure local regulations and site

procedures are followed.

Never attempt to open the detector or junction box when flammable

gas is present.

Ensure that the associated control panel is inhibited so as to prevent

false alarms.

4.1 Commissioning Procedure

a.

Open the junction box of the detector by loosening the tamper proof grub

screw and removing the lid by rotating it anti-clockwise.

b.

Remove the amplifier and check that all electrical connections have been

made and are correct as per Diagram 3.

c.

Replace the amplifier and close the junction box ensuring that all screws

have been re-fitted correctly.

d.

Apply power to the detector. The status LED will show a steady green

indicating normal operation.

e.

Leave the detector to stabilise for 1-2 hours. 

Zeroing the detector (ZERO Mode):

f.

Place the end of ‘CRO-Mag’ over the ‘MENU’. Green Status LED will flash.

Decimal point above ‘ZERO’ will illuminate. Display backlight will illuminate.

Decimal point above ‘INHIBIT’ may flash if the option has been internally

selected.

g.

With no target gas present at the detector, place the end of the ‘CRO-

Mag’ key over the ‘UP’ or ‘DOWN’ arrow pads to make the display read

zero. 

Note: Oxygen detectors may be zeroed in fresh air 

Calibrating the detector (CAL mode):

h.

Place the end of ‘CRO-Mag’ over the MENU pad. The decimal point above

the word CAL will illuminate. Other indications remain unchanged.

i.

Apply calibration gas to the detector at a flow rate of 0.5 litres/min.

CONTROL EQUIPMENT

SAFE AREA

CONTROL EQUIPMENT

SAFE AREA

+V

0 V 

SOURCE

10–30 V

10–30 V

4–20 mA

4–20 mA

0  V

0  V

TXGARD-PLUS

TXGARD-PLUS

SINK

+V

0 V 

2

3

1

2

3

1

Diagram 3 

: Electrical connections to TXgard-Plus

Reviews: