INSTALLATION SHEET

CONNECTION

WARNING

SSR - DIN-RAIL MOUNT

MINI

C.MC.DEF.___EN

WARNING

DANGER

RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE

•   

Confirm that the product power supply voltage and its tolerances are compatible

     with those of the electrical network.

•   

The product's side panels may be hot, allow the product to cool before touching.

•   

Follow proper mounting instructions including torque values.

•   

Do not allow liquids or foreign objects to enter this product.

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Turn off power supply before working on this equipment.

Failure to follow these instructions can result in death, serious 

injury or equipment damage.

!

For more information please go to 

www.crouzet.com

IMPORTANT CONSIDERATIONS

TRANSIENT VOLTAGE

Electrical equipment should be installed, operated, serviced and maintained only by 
qualified personnel. No responsibility is assumed by Crouzet for any consequences 
arising out of use of this manual. Be sure to use input and output voltage within 
operating ranges.

        WARNING: 

The product’s side panels may be hot, allow the product to cool before 

touching. Please follow mounting instructions. Failure to follow these instructions can 
result in serious injury or equipment damage.

In AC power lines, transient voltages are common and may pose a risk for the 
operation, load and reliability of the SSR. In Crouzet SSR, the transient protection can 
rise 800 V (please refer to product datasheet).

User may also use external transient protection to the SSR for additional protection 
(please refer to product datasheet).   

!

CONNECTION

DERATING CURVES

SOLID

4 mm²

AWG12

2.5 mm²

AWG14

4 mm²

AWG12

2.5 mm²

AWG14

(No ferrule)

STRANDED

(With ferrule)

SOLID

(No ferrule)

STRANDED

(With ferrule)

SOLID

(No ferrule)

STRANDED

(With ferrule)

SOLID

(No ferrule)

STRANDED

(With ferrule)

4 mm²

AWG12

2.5 mm²

AWG14

4 mm²

AWG12

2.5 mm²

AWG14

NUMBER OF WIRES - Direct connection with wires with or without ferrules

1

2

1

2

NUMBER OF WIRES - Direct connection with wires with or without ferrules

INPUT WIRING

OUTPUT WIRING

SCREWDRIVER TYPE:  

POZIDRIV 2

RECOMMENDED TIGHTENING TORQUE:

M5 SCREW N.M
Min 0.4 / Max 0.5

RECOMMENDED TIGHTENING TORQUE:

M5 SCREW N.M
Min 0.4 / Max 0.5

 

C

ur

re

nt

 (A

)

Ambient Temperature (°C)

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

0

10

20

30

40

50

60

70

80

90

C

ur

re

nt

 (A

)

Ambient Temperature (°C)

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

0

10

20

30

40

50

60

70

80

90

100

GNR Mini - 4 A

 

GNRD Mini - 4 A

 