INSTALLATION SHEET
MOUNTING INSTRUCTIONS
SSR - DIN-RAIL MOUNT
MINI
GN
R Mini
GN
RD Mini
AC OUTPUT
DC OUTPUT
CROUZET SOLID STATE RELAYS - DIN RAIL MOUNT PRODUCTS
have been developed to offer all the advantages of electronic switching technology. The 12 mm industrial
housing is quick to install. The product is compact and reliable. Please refer to the data sheet available on
www.crouzet.com
DIN Rail - AC Output Single Phase
• Output Current of 4 Amps
• Output Voltage of 12-275 V
a
& 12-460 V
a
• Control Voltage of 6-30 V
c
, 12-30 V
a
/ 8.5-30 V
c
• Special Zero Cross Switching
DIN Rail - DC Output
• Output Current of 4 Amps
• Output Voltage of 2-60 V
c
• Control Voltage of 5-30 V
c
, 90-240 V
z
1.
Locate rail and align with the top part of the DIN clip in the back of the SSR
2.
Using reasonable force, push the SSR in the direction of the arrows
3.
To remove, place the screwdriver on the clip and push in the direction shown
WARNING:
Removing product from RAIL DIN incorrectly by not using the
appropriate tool will damage the latching system
!
C.MC.DEF._____.EN
!
WARNING:
The user should protect heat sensitive materials as well as people
against any contact with the product.
For correct cooling, the SSR needs air convection. Less air convection produces an
abnormal heating. In the event there is no space between two SSRs, reduce the load
current. Forced cooling (ex. fan inside the cabinet) significantly improves the thermal
performance.
For more information please go to
www.crouzet.com
MOUNTING ON DIN RAIL
DISMOUNTING
PART NUMBER NOMENCLATURE
GN
R Mini
GNRM
4
D2
A
4:
4A
D2:
6-30 V
c
B1:
12-30 V
a
|
12-30 V
a
A:
12-275 V
c
|
Special Zero Cross
B:
12-460 V
a
|
Special Zero Cross
GNR Mini
Series
Series
Output
Current
Control
Voltage
Output
Voltage
GN
RD Mini
GNRDM
4
D1
C
4:
4A
D1:
5-30 V
c
A1:
90-240 V
z
C:
2-60-240 V
z
|
DC Switching
GNRD Mini
Series
Series
Output
Current
Control
Voltage
Output
Voltage
WIRING DIAGRAMS
GN
R Mini
GN
RD Mini
2
(- )
1
(+)
LOAD
DC
-
+
4(
-
)
3(+)
4(-)
3(+)
2
1
AC
LOAD
1
1
1.
Protection Equipment: Short circuit protection
GNRDM4D1C & GNRDM4A1C:
it is recommended to add an overvoltage protection
2
3
DIN rail connected to protection
wire (ground)
1