42
© 2014 All rights reserved. Data subject to change without notice.
GEM-II - Operation Manual
Rev. E | 2014.10
7.7 Time Delays for Relay operations
GEM offers a wide range of time delay settings that are user configurable. If the GEM has been
equipped with the LED digital display option, read the values on the display as you change them
to suit your application. If the GEM does not have a digital display, you will require a digital volt
meter set to volts DC, one decimal point. The following tables are a guideline to follow to achieve
desired time delays. Voltage reference is 0 - 4 VDC.
VOLT READING AT TEST POINTS
TIME DELAY IN MINUTES
0
N/A
0.02
0.1
0.04
0.2
0.06
0.3
0.08
0.4
0.10
0.5
0.12
0.6
0.14
0.7
0.16
0.8
0.18
0.9
0.20
1.0
0.22
1.1
0.24
1.2
0.26
1.3
0.28
1.4
0.30
1.5
0.32
1.6
0.34
1.7
0.36
1.8
0.38
1.9
0.40
2.0
0.42
2.1