26
FnIO MODBUS Adapter NA-9189
FnIO S-Series
Copyright(C) CREVIS Co.,Ltd Support +82-31-273-6453 URL : www.crevis.co.kr
Input Process Image Mode#3
(Compressed Input Processing Data without Status)
Addr.
#15 #14 #13 #12 #11 #10 #9
#8
#7
#6
#5
#4
#3
#2
#1
#0
0x0000
Analog Input Ch0 high byte (Slot#3)
Analog Input Ch0 low byte (Slot#3)
0x0001
Analog Input Ch1 high byte (Slot#3)
Analog Input Ch1 low byte (Slot#3)
0x0002
Analog Input Ch0 high byte (Slot#8)
Analog Input Ch0 low byte (Slot#8)
0x0003
Analog Input Ch1 high byte (Slot#8)
Analog Input Ch1 low byte (Slot#8)
0x0004
Discrete In low 8pts (Slot#4)
Discrete In 8pts (Slot#2)
0x0005
Discrete In 8pts (Slot#6)
Discrete In high 8pts (Slot#4)
0x0006
Discrete In high 8pts (Slot#9)
Discrete In low 8pts (Slot#9)
0x0007 Discrete In 4pts
(Slot#10)
Discrete In 4pts
(Slot#7)
Discrete In 4pts
(Slot#5)
Discrete In 4pts
(Slot#1)
* FnBus uses the byte-oriented register mapping.
* Size of input image bit is size of input image register *16.
Input Assembly Priority :
1)
Analog Input Data (Word type)
2)
8 or 16 points Discrete Input Data (Byte type)
3)
4 points Input Data (Bit type)
4)
2 points Input Data (Bit type)