3.5.8. Parameter Data
-. Valid Parameter length : 6 Bytes
-. Parameter Data
Bit No
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Byte 0
Fault Action for
Channel 3
Fault Action for
Channel 2
Fault Action for
Channel 1
Fault Action for
Channel 0
00 : Fault Value 01 : Hold last state 10 : Low Limit 11 : high Limit
Byte 1
Fault Action for
Channel 7
Fault Action for
Channel 6
Fault Action for
Channel 5
Fault Action for
Channel 4
00 : Fault Value 01 : Hold last state 10 : Low Limit 11 : high Limit
Byte 2
Fault Action for
Channel 11
Fault Action for
Channel 10
Fault Action for
Channel 9
Fault Action for
Channel 8
00 : Fault Value 01 : Hold last state 10 : Low Limit 11 : high Limit
Byte 3
Fault Action for
Channel 15
Fault Action for
Channel 14
Fault Action for
Channel 13
Fault Action for
Channel 12
00 : Fault Value 01 : Hold last state 10 : Low Limit 11 : high Limit
Byte 4
Fault Value Low Byte
Byte 5
Not used
Fault Value high Byte
Analog Input Ch8
Analog Input Ch9
Analog Input Ch10
Analog Input Ch11
Analog Input Ch12
Analog Input Ch13
Analog Input Ch14
Analog Input Ch15