ZUMMESH-JBOX-20A-SW/ZUMMESH-JBOX-5A-LV/ZUMMESH-JBOX-16A-LV/ZUMMESH-JBOX-20A-PLUG/ZUMMESH-JBOX-PSU
Z
ū
m™ J-Box Load Controller
Installation Guide
Description
The Crestron
®
junction box-mounted zone controllers deliver intelligent lighting control
with essential features for energy efficiency. Available for 20 A switching, 5 A or 16 A
0-10 V dimming, and 20 A plug load control, each ZUMMESH-JBOX model wirelessly
connects to Z
ū
m daylight sensors, occupancy sensors, vacancy sensors, keypads, and
dimmers (all sold separately) over the Z
ū
m mesh network, providing intelligent lighting
control based on the amount of natural light and the presence of people in a space. The
Z
ū
m J-Box Zone Controllers offer a powerful lighting control solution for every space
within the Z
ū
m network.
A basic single-room Z
ū
m system consists of Z
ū
m mesh devices, i.e., dimmers, switches,
keypads, and sensors. The Z
ū
m mesh devices in the room communicate directly with
each other without the need for a centralized gateway or processor.
To monitor or control the room from a centralized Crestron control system, use the
ZUMMESH-NETBRIDGE.
NOTE
: The ZUMMESH-NETBRIDGE requires a J-box device to provide power.
For quick network setup, use the Z
ū
m app on a smartphone or tablet.
Additional Resources
Visit the product page on the Crestron website (www.crestron.com)
for additional information. Use a QR reader application on your
mobile device to scan the QR image.
Installation
WARNING
: To avoid fire, shock, or death, turn off the power at the circuit breaker or
fuse and test that the power is off before wiring!
NOTES
: Observe the following points:
• Install and use this product in accordance with appropriate electrical codes and
regulations.
• A licensed electrician should install this product.
To install a switch or dimmer, do the following:
1. Turn the power off at the circuit breaker.
3. Mount the J-box device to the J-box.
2. Wire the device as shown in the following diagrams.
ZUMMESH-JBOX-5A-LV, ZUMMESH-JBOX-16A-LV,
and ZUMMESH-JBOX-20A-SW Wiring
Test the Loads
Press the TEST button to toggle the connected loads.
Press and hold the TEST button to cycle dim the connected loads (dimmer models only).
ZUMMESH-JBOX-PSU Wiring
NOTE
: The 0–10 V dim - and 0–10 V dim + wires are not present on the
ZUMMESH-JBOX-20A-SW.
ZUMMESH-JBOX-20A-PLUG Wiring
SPECIFICATION
DETAILS
Power Requirements
Line Power
100-277 Vac, 50/60 Hz
Idle State Power
Consumption
1 W
Expansion Port
Expansion port allows connection of an
accessory such as a Z
ū
m Network Bridge
(ZUMMESH-NETBRIDGE) or HVAC Contact
Closure Module (ZUM-CCO)
Models
ZUMMESH-JBOX-16A-LV /
ZUMMESH-JBOX-5A-LV
Switched Output
16 A at 100-277 Vac, 50/60 Hz (20 A, de-rated
to 80%)
5 A at 100-277 Vac, 50/60 Hz
0-10V Output
60 mA Sink or Source
DIM Load Type
LED driver (4-wire), Fluorescent, Incandescent,
MLV, ELV
Functionality
Controlled by keypads, occupancy or vacancy,
and daylight sensors.
Expansion Port
Allows connection of Z
ū
m Network Bridge or
Relay Contact Closure Module
ZUMMESH-JBOX-20A-SW
Switched output
20 A high in-rush (de-rated to 80%), zero cross
switching
Switch Load Types
0-10 V LED driver, Fluorescent ballast (4-wire), 60
mA max current sink or source
Functionality:
Controlled by keypads and occupancy or
vacancy sensors
Expansion Port:
Allows connection of Z
ū
m Network Bridge or
Relay Contact Closure Module
ZUMMESH-JBOX-20A-PLUG
Switched output
20 A high in-rush, zero cross switching for control
of receptacles
Functionality
Controlled by occupancy or vacancy sensors to
energize receptacles when the room is occupied.
Note that the output defaults to energized state
after a power cycle.
Expansion Port
Allows connection of Z
ū
m Network Bridge or
Relay Contact Closure Module
ZUMMESH-JBOX-PSU
Functionality
Provides power for Z
ū
m Network Bridge when
other J-box devices are not available.
Expansion Port
Allows connection of Z
ū
m Network Bridge or
Relay Contact Closure Module
Enclosure
Housing
Plastic, white, UL
®
standard 5VA rated
Mounting
Mounts in a 4˝ x 4˝ junction box via 1/2 in conduit
knockout;
Rated for mounting in plenum spaces, UL
standard 2043
Environmental
Temperature
32° to 104 °F (0° to 40 °C)
Humidity
10% to 90% RH (noncondensing)
Dimensions
Height
3.25 in (83 mm)
Width
4.17 in (106 mm)
Depth
1.31 in (33 mm)
Weight
0.4 lbs (7 oz)
Neutral (white)
To 0-10 V
Controlled load
0-10 V dim + (purple)
0-10 V dim - (gray)
Switched output (red)
Neutral
(white)
Hot (black)
100-277 Vac power
from breaker
Neutral (white)
15 or 20 A receptacle
Switched output (red)
Hot (black) to
unswitched
receptacles
Neutral (white)
Hot (black)
100-277 Vac power
from breaker
Neutral (white)
Hot (black)
100-277 Vac power
from breaker