Supplemental Guide – DOC. 7874D
PC-200/PC-300: 8-Outlet Power Conditioners
•
13
Limits
Use the Limits section of the System Settings page to set various system limits for the
power conditioner.
System Settings - Limits
The following settings can be configured:
•
Under voltage cutoff (V): Sets the undervoltage cutoff in volts (The power
conditioner shuts off power to the ac outputs when the ac input voltage is detected
to have gone under this number.)
•
Over voltage cutoff (V): Sets the overvoltage cutoff in volts (The power conditioner
shuts off power to the ac outputs when the ac input voltage is detected to have
gone over this number.)
•
Over current cutoff (A): Sets the overcurrent cutoff in amperes (The power
conditioner shuts off if the combined amperes of the ac outputs are detected to
have gone over this number.)
•
Temperature units: Selects the unit of measurement for the power conditioner
temperature (Celsius or Fahrenheit)
•
Temperature cutoff: Sets the temperature cutoff in the selected unit of
measurement (The power conditioner shuts off if its temperature is detected to
have gone over this number.)
•
Power cycle delay (secs): Sets the duration that the power to an outlet cycles off
before powering back on in seconds
Click Save at the bottom of the page to save the configuration. Click Reset to clear any
pending changes.
Ping Monitor
Use the Ping Monitor section of the System Settings page to configure the ping monitor
settings for the power conditioner. For the PC-300, each of the eight outlets can be
assigned to ping a different device domain/IP. For the PC-200, outlets 1–6 can be assigned
to ping a different device domain/IP.
When activated, the ping monitor pings the device connected to a chosen outlet and waits
for a response. During every interval, up to four ping attempts are made. If the device does
not respond after four attempts, the power is cycled for the associated outlet, which forces
a reboot of the hardware that has locked up or become otherwise unresponsive.
NOTE:
The ping monitor is temporarily inactive when the associated outlet is switched off
manually.