Photocell Response Time (Pr)
This
Setup
mode is used to adjust the response time of the lights to a change in the
photocell reading. Valid values are 10 seconds, 30 seconds, 1 minute, 2 minutes,
5 minutes. The default value is 1 minute.
To adjust the response time of the photocell:
•
Enter
Setup
mode and scroll to the “Pr” option (using the
^
and
v
buttons).
Press either the top or bottom portion of the raise/lower button. The 2-digit
display indicates the response time.
•
Use the
^
and
v
buttons (located next to save/cancel) to increase or decrease
the response time.
•
Press
Save
to save the new setting or
Cancel
to retain the original setting.
NOTE:
The CLS-C6 temporarily utilizes a faster response time when there
are rapid changes in light (such as when shades or blinds are opened or
closed). If daylight in the room has increased, the response time is increased
to 10 seconds. If daylight in the room has decreased, the response time is 2
seconds. Under normal operation, the CLS-C6 implements a gradual
response time.
Restore Factory Defaults (Fd)
This procedure is used to restore all settings to their factory defaults.
1.
First enter
Setup
mode and then scroll to the “Fd” option (using the
^
and
v
buttons). Then press the up/down button (either top, bottom, or both), and
hold for 5 seconds.
2.
This procedure is locked in, and the
Save
LED flashes. (If the button is
released before 5 seconds are up, nothing happens.) Press
Save
all
configuration items are set to their factory default values. (Press
Cancel
and
the unit exits
Setup
mode without changes.) The factory default
configuration does not include any remote devices. To re-initialize remote
devices, run Auto-discover after this function. Running the factory default
function does modify the MNET ID of the CLS-C6.
3.
The save process may take a few seconds. During this time, the
Save
LED
is lit steady, and the two-digit display shows “—”. When the process is
complete, the LEDs extinguish.
Refer to “Appendix C: RS-232 Commands” on page 58 for a list of the system
default values.
Configuring with iLux Designer
The Crestron iLux Designer program software supplied with all of the CLS-C6 series
units configures the CLS-C6 as an independent, standalone device or as a network
device in a Crestron network control system (Cresnet system).
To configure the CLS-C6 using the iLux Designer, use a direct serial connection as
described in “Establishing Communication” on page 31.
NOTE:
Connecting the serial cable to the front panel of the CLS-C6 disconnects the
control system network.