Problem Solving
Troubleshooting
The following table provides corrective action for possible trouble situations. If
further assistance is required, please contact a Crestron customer service
representative.
GLS-EM-MCU Troubleshooting
TROUBLE
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
Device does not
function.
Device is not
communicating with the
network.
Use Crestron Toolbox to poll
the network. Verify network
connection to the device.
Device is not powered
correctly.
Check that voltage levels are
correct as measured from
each phase to neutral.
CT1
–
CT3
LED is
flashing.
GLS-EM-CT is
incorrectly wired.
Ensure that black and white
wires are properly connected
to the
BLK
and
WHT
terminals on the device.
GLS-EM-CT is
improperly installed.
Verify that device is facing the
proper direction. Ensure that
the
THIS SIDE TOWARDS
SOURCE
label faces the
source.
Loss of
functionality due
to electrostatic
discharge.
Improper grounding.
Check that all ground
connections have been made
properly.
Reference Documents
The latest version of all documents mentioned within the guide can be obtained from
the Crestron Web site (
List of Related Reference Documents
DOCUMENT TITLE
GLS-EM-MCU Installation Guide
Further Inquiries
To locate specific information or to resolve questions after reviewing this guide,
contact Crestron's True Blue Support at 1-888-CRESTRON [1-888-273-7876] or
refer to the listing of Crestron worldwide offices on the Crestron Web site
(www.crestron.com/offices) for assistance within a particular geographic region.
To post a question about Crestron products, log onto the Online Help section of the
Crestron Web site (www.crestron.com/onlinehelp). First-time users must establish a
user account to fully benefit from all available features.