Load Connection Example for the DIN-1DIMU4
Neutral
Line
Ground
Neutral
Line
Ground
120/240 Volts
Load
120/240 Volts from
Breaker
WARNING
: Prior to connecting the device, turn off power at the circuit
breaker. Failure to do so may result in serious personal injury or damage
to the device. Restore power after all connections have been made.
CAUTION
: Connecting this device to the wrong type of load or
short circuiting the load can cause severe product damage
.
Each load
should be tested to identify a short circuit condition prior to wiring the
load to the module.
NOTE
: Install in accordance with all local and national electric codes.
NOTE
: High-voltage connections accept 2.5 mm
2
(12 AWG) wire. Wire
should be stripped to 8 mm (1/3 inch). Tighten terminal blocks to 0.5 Nm
(5 in-lbs).
NOTE
: Use copper wire only. For high-voltage connections, use wire
rated for at least 75º C (167º F).
NOTE
: The DIN-1DIMU4 power feed must be protected by a 10 A (trip
curve C) breaker or equivalent.
NOTE
: The DIN-1DIMU4 outputs must be used for control of
permanently installed lighting loads only.
Operations & Installation Guide – DOC. 6668D DIN Rail Universal Dimmer: DIN-1DIMU4
•