![Crestron CP3 Operation Manual Download Page 13](http://html.mh-extra.com/html/crestron/cp3/cp3_operation-manual_2683660013.webp)
Crestron
CP3 & CP3N
3-Series Control Systems
Operations Guide – DOC. 7316C
3-Series Control Systems: CP3 & CP3N
•
9
Connectors, Controls & Indicators
#
CONNECTORS*,
CONTROLS &
INDICATORS
DESCRIPTION
1
COMPUTER
Pin 1 Pin 2
Pin 4 Pin 3
(1) USB Type B female, USB 2.0 computer
console port (cable included); For setup only
PIN
DESCRIPTION
1
+5 VDC
2
Data -
3
Data +
4
Ground
2
PWR LED
(1) Green LED, indicates operating power
supplied from power pack or Cresnet network
3
NET LED
(1) Amber LED, indicates communication with
the Cresnet system
4
MSG LED
(1) Red LED, indicates control system has
generated an error message
5
RESET BUTTONS
HW-R
– (1) Recessed push button for
hardware reset
SW-R
–(1) Recessed push button for software
reset
6
RELAY OUTPUT (1 – 8)
1
2
3
4
(2) 8-pin 3.5 mm detachable terminal blocks
comprising (8) normally open, isolated
relays; Rated 1 amp, 30 volts ac/dc;
MOV arc suppression across contacts
7
I/O (1-8)
1 2 3 4 5 6 7 8 G
(1) 9-pin 3.5 mm detachable terminal block
comprising (8) “Versiport” digital input/output
or analog input ports (referenced to GND);
Digital Input: Rated for 0-24 volts dc, input
impedance 20
kΩ
, logic threshold >3.125 V
low/0 and <1.875 V high/1;
Digital Output: 250 mA sink from maximum
24 volts dc, catch diodes for use with “real
world” loads;
Analog Input: Rated for 0-10 volts dc,
protected to 24 volts dc maximum, input
impedance 21
kΩ
with pull-up resistor
disabled;
Programmable 5 volts, 2
kΩ
pull-up resistor
per pin
8
IR – SERIAL OUTPUT
(1-8)
S
1
2
3
4
G S G S G S G
(2) 8-pin 3.5 mm detachable terminal blocks
comprising (8) IR/Serial output ports;
IR output up to 1.2 MHz;
1-way serial TTL/RS-232 (0-5 volts) up to
115.2k baud
(Continued on following page)