CLW-SW1, SWS1, & SLVS1(W/A/B)
approved connectors (supplied by others) to
make Class 2 connections inside the wallbox.
Inner Sections of Multiganged Switches
•
CAUTION
: TO REDUCE THE RISK OF
OVERHEATING AND POSSIBLE DAMAGE
TO OTHER EQUIPMENT, DO NOT INSTALL
TO CONTROL A RECEPTACLE.
•
Wiring: Use copper wire only. For supply
connection, use wires rated for at least 75°C.
•
Load Type: The -SW1, -SWS1, and -SLVS1 are
designed for use with permanently installed
incandescent, fluorescent (non-dimmable), low
voltage, neon/cold cathode, HID, general
purpose fan, or tungsten halogen lighting.
•
Temperature: The -SW1, -SWS1, and -SLVS1
are designed to be used where temperatures are
between 32° to 104°F (0° to 40°C).
•
Wallboxes: Devices mount in standard
wallboxes. For easy installation, Crestron
recommends using 3 ½” deep wallboxes. Several
devices can be installed in one wall box
(multigang). This requires the removal of side
sections (refer to diagram on page 3) and the
derating of the switching device. For a smooth
appearance, one-piece multigang faceplates (not
supplied) can be installed.
REMOVE INNER SECTIONS
DO NOT REMOVE OUTER SECTIONS
The load capacity must also be derated. The
following charts provide derating information for
various applications.
Derating Information for Incandescent, Tungsten Halogen,
and Electronic Low Voltage Applications
Part Number
No Side
Removed
One Side
Removed
Two Sides
Removed
-SW1 1000W
600W 400W
-SWS1
1000W
600W
400W
-SLVS1
No Derating Necessary
•
Other Switch Devices: Mechanical 3- or 4-way
switches will not work with the -SW1, -SWS1,
or -SLVS1.
•
Spacing: If mounting one device above another,
leave at least 4 ½” vertical space between them.
Derating Information for Magnetic Low Voltage and
Neon/Cold Cathode Applications
*
Part
Number
No Side
Removed
One Side
Removed
Two Sides
Removed
-SW1
1000VA/750W 600VA/450W 400VA/300W
-SWS1
1000VA/750W
600VA/450W
400VA/300W
-SLVS1
No Derating Necessary
Multigang Installations
In multigang installations, several controls are grouped
horizontally in one wallbox. For a smooth appearance,
one-piece multigang faceplates (not supplied) can be
installed.
* VA ratings are for input power to the transformer. If you do not
know the input power requirement of the transformer, use the bulb’s
wattage rating to determine proper rating.
1. When combining controls in a wallbox, remove
inner side sections prior to wiring (refer to the
following figure).
Installation Guide – DOC. 6251
Stand Alone Wall Box Switch: CLW-SW1, SWS1, & SLVS1
•
3