Terminal Block & Module 

Module Installation 

CAUTION:  

Module contains electrostatic sensitive 

devices (ESDs); unit must be handled from metal chassis 
– do not touch PC board or components. 

NOTE:  

Modules are to be installed after enclosure has 

been completely wired. Refer to the terminal block 
installation procedure on page 2 for details.  

1.  Use the four supplied self-tapping pan Phillips 

screws (8B x ¼-inch (6 mm) length) to secure 
the module to the enclosure. 

2.  As shown in the wiring diagrams (next column), 

connect the wires from the module to the 
terminal block. Each wire exits the module 
directly in line with, and is the same color as, the 
terminal to which it should be connected. Wires 
are pre-stripped to 12 mm. Tighten to 1 Nm.  

3.  If the module is being installed above another 

module within the enclosure, attach the supplied 
module interconnect cable between the two 
modules. The illustration below depicts the area 
within a double-wide enclosure where the 
corners of four modules meet.  

NOTE:  

One wire on the module interconnect cable 

may be a different color from the rest. The color has 
no bearing on its orientation during installation.  

Use Module Interconnect Cable to Wire Module to Module  

MODULE

INTERCONNECT

CABLE ATTACHED

CONNECTION

NOT

MADE

 

4.  Turn on the circuit breakers and verify that the 

green 

PWR 

LED on the module lights, the 

breakers do not trip, and power is delivered to 
the loads.  

5.  Turn off the circuit breakers and remove the 

bypass jumpers on the brown and red sections of 
the terminal block. The jumpers on the blue 
sections of the terminal block must remain 
installed. Refer to the figures in the next column 
for a close-up of the jumpers.  

NOTE:  

Before the bypass jumpers are removed, the 

Crestron Professional Automation Computer (PAC2), 

which provides control to the system, should be 
properly connected and contain a valid program to 
provide control of the module.  

Wiring Diagram of the Terminal Block to the Module 
(Single-wide and Left Side Double-wide Enclosures) 

ENLARGEMENT DETAIL:

BYPASS JUMPERS ON 
RED AND BROWN 
SECTIONS HAVE BEEN 
REMOVED AFTER 
LOOSENING ALL 
SCREWS.

JUMPERS ON BLUE 
SECTIONS ARE NOT 

REMOVED.

JUMPERS INSTALLED

BYPASS

JUMPERS 

REMOVED

BLUE

 TO LOADS

BROWN FROM BREAKER

RED

 TO LOADS

RED

 TO LOADS

BROWN FROM BREAKER

BLUE FROM BREAKER PANEL

BLUE

 TO LOADS

BLUE FROM BREAKER PANEL

 

Wiring Diagram of the Terminal Block to the Module 
(Right Side Double-wide Enclosures) 

BLUE FROM BREAKER PANEL

BROWN FROM BREAKER

BLUE

 TO LOADS

BLUE FROM BREAKER PANEL

RED

 TO LOADS

BROWN FROM BREAKER

RED

 TO LOADS

BLUE

 TO LOADS

BYPASS

JUMPERS 

REMOVED

ENLARGEMENT DETAIL:

BYPASS JUMPERS ON RED 

AND BROWN SECTIONS 

HAVE BEEN REMOVED 

AFTER LOOSENING ALL 

SCREWS.

JUMPERS ON BLUE 
SECTIONS ARE NOT 

REMOVED.

JUMPERS

INSTALLED

 

6.  Turn on the circuit breakers. 

NOTE:  

Power must be supplied to LINE 1 for the 

module to communicate with the control system or 
for any of the circuits to operate. 

Installation Guide – DOC. 6411A 

Terminal Block & Module:  CLTI- & CLXI-2DIM8  

  3  

 

Summary of Contents for CLTI-

Page 1: ...DULE ROUNDING ERMINAL BLOCK TERMINAL BLOCK INSTALL INTO LOWEST AVAILABLE SPACES NOTE The two input lines must be the same phase or split phase NOTE When connecting to an Arc Fault Breaker the load should not exceed 1000 watts Terminal Block Module Locations Double wide Enclosure Installation The terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electricia...

Page 2: ...OUP 2 FEED DIM5 DIM8 FROM 16 AMP CIRCUIT BREAKER NEUTRAL AREA FOR MODULE LOCATION LABEL TO LOAD S LEFT SIDE WIRING LABEL TERMINAL BLOCK GND GROUNDING TERMINAL BLOCK NEUTRAL GROUP 1 FEED DIM1 DIM4 FROM 16 AMP CIRCUIT BREAKER LINE 1 LINE 2 3 Use the two supplied self tapping pan Phillips screws 8B x 6 mm length to secure the terminal block to the Crestron Automation Enclosure CAUTION Bypass jumpers ...

Page 3: ... is delivered to the loads 5 Turn off the circuit breakers and remove the bypass jumpers on the brown and red sections of the terminal block The jumpers on the blue sections of the terminal block must remain installed Refer to the figures in the next column for a close up of the jumpers NOTE Before the bypass jumpers are removed the Crestron Professional Automation Computer PAC2 which provides con...

Page 4: ...lso log onto the online help section of the Crestron website www crestron com onlinehelp to ask questions about Crestron products First time users will need to establish a user account to fully benefit from all available features 3 Press the SETUP button again for each output 4 After turning on the last output press the SETUP button again to turn on all outputs 5 Press the SETUP button once more t...

Page 5: ...r 90 days batteries and incandescent lamps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for whic...

Page 6: ...Terminal Block Module Crestron CLTI CLXI 2DIM8 6 Terminal Block Module CLTI CLXI 2DIM8 Installation Guide DOC 6411A This page is intentionally left blank ...

Reviews: