STEP 2:
Although no routine maintenance is required to keep the emergency driver functional,
it should be checked periodically to ensure that it is working. The following schedule is
recommended:
• Visually inspect the charging indicator light monthly. It should be illuminated.
• Test the emergency operation of the fixture at 30-day intervals for a minimum of 30
seconds. When the test switch is depressed, the LED array should operate.
• Conduct a 90-minute discharge test once a year. The LED array should operate for at
least 90 minutes.
If the luminaire fails any of these checks, consult service personnel.
REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH
CIRCUIT.
ELECTRICAL CONNECTIONS
NOTE:
The emergency driver must be fed from
the same branch as the AC Driver.
STEP 1:
Using customer supplied 90°C minimum rated wire
connectors, make the following electrical connections:
a. Connect the black luminaire lead to the
unswitched voltage supply lead.
b. Connect the white/red luminaire lead to
the switched supply switched.
c. Connect white luminaire lead to the neutral supply lead.
d. Connect ground bare or green/yellow wire
lead to the supply ground lead.
e. If 0/1-10V Dimming is used, connect the violet lead
to the supply positive dimming lead. If dimming is
not being used ensure to cap off the violet lead.
f. If 0/1-10V Dimming is used, connect the gray lead
to the supply negative dimming lead. If dimming is
not being used ensure to cap off the gray lead.
STEP 2:
Locate the two red leads in the junction box and connect them using
customer supplied connector.
WHITE
DIM (-) GREY
DIM (+) VIOLET
VIOLET
GREY
SUPPL
Y WIRING
(DIMMING OPTIONAL)
LUMINAIRE
GROUND
BARE OR
GREEN/YELLOW
WHITE/RED
SWITCHED HOT
BLACK
UNSWITCHED HOT
** NOTE: DO NOT mate leads until installation
is complete and AC power is supplied
**RED
**RED
WHITE
NEUTRAL
Test Switch
Large Trim Ring
Small Trim Ring
Ceiling
5
FCC NOTICE
CAUTION:
Changes or modifications not expressly approved could void your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his own expense.
CAN ICES-003 (A)/NMB-003 (A)