STEP 2:

Although no routine maintenance is required to keep the emergency driver functional, 
it should be checked periodically to ensure that it is working. The following schedule is 
recommended: 

•  Visually inspect the charging indicator light monthly. It should be illuminated. 
•  Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 

seconds. When the test switch is depressed, the LED array should operate. 

•  Conduct a 90-minute discharge test once a year. The LED array should operate for at 

least 90 minutes.

If the luminaire fails any of these checks, consult service personnel.
REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH 
CIRCUIT.

ELECTRICAL CONNECTIONS 

NOTE: 

The emergency driver must be fed from 

the same branch as the AC Driver.

STEP 1:

Using customer supplied 90°C minimum rated wire 
connectors, make the following electrical connections: 

a.  Connect the black luminaire lead to the 

unswitched voltage supply lead. 

b.  Connect the white/red luminaire lead to 

the switched supply switched.

c.  Connect white luminaire lead to the neutral supply lead.
d.  Connect ground bare or green/yellow wire 

lead to the supply ground lead.

e.  If 0/1-10V Dimming is used, connect the violet lead 

to the supply positive dimming lead. If dimming is 
not being used ensure to cap off the violet lead. 

f.  If 0/1-10V Dimming is used, connect the gray lead 

to the supply negative dimming lead. If dimming is 
not being used ensure to cap off the gray lead.

STEP 2:

Locate the two red leads in the junction box and connect them using 
customer supplied connector.

WHITE

DIM (-) GREY

DIM (+) VIOLET

VIOLET

GREY

SUPPL

Y WIRING

(DIMMING OPTIONAL)

LUMINAIRE

GROUND

BARE OR

GREEN/YELLOW

WHITE/RED

SWITCHED HOT

BLACK

UNSWITCHED HOT

** NOTE: DO NOT mate leads until installation 
is complete and AC power is supplied

**RED

**RED

WHITE

NEUTRAL

Test Switch

Large Trim Ring

Small Trim Ring

Ceiling

5

FCC NOTICE

CAUTION:

 Changes or modifications not expressly approved could void your authority to use this equipment. 

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are 
designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment 
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful 
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will 
be required to correct the interference at his own expense.
CAN ICES-003 (A)/NMB-003 (A)

Reviews: