TROUBLESHOOTING:
Out of the box, if the LOAD does not turn on when power is applied:
Perform TEST mode to verify proper functionality of the load type
•
If TEST mode fails, check Wiring with power off.
•
If wired correctly, check to see if Blue LED is blinking.
•
If Blue LED is blinking, then perform a RESET (See RESET
section).
•
If Blue LED is on solid or off, call Cree Customer Service.
•
If you have done a RESET, and the LOAD is still off, call Cree
Customer Service.
If LOAD is unresponsive use Cree Configuration Tool to verify
configuration.
FCC NOTICE
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Any changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate
the device.
This device has been tested and found to comply with the limits for
a Class A digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the device is operated in a commercial environment.
This device generates, uses, and can radiate radio frequency energy
and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of
this device in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his
own expense.
In addition, this device complies with ICES-003 of the Industry Canada
(IC) Regulations.
ELECTRICAL CONNECTIONS-
850 AND 1250 LUMEN WITH 120V/277V DRIVER WITH CREE SMARTCAST™ TECHNOLOGY (0-10V)
OR
2000 AND 3000 LUMEN WITH 120/277V DRIVER WITH CREE SMARTCAST™ TECHNOLOGY (0-10V)
NOTE: Luminaire is intended to be wired to a specific voltage.
Make sure that supply voltage matches voltage on electrical
label next to the junction box. Connecting luminaire to voltage
other than that specified on the label may result in luminaire
damage and/or improper luminaire operation. The emergency
driver must be fed from the same branch as the AC Driver.
STEP 1:
Supply connections can be brought to the junction
box using customer supplied conduit.
STEP 2:
Using customer supplied 90°C minimum rated wire connectors,
make the following electrical connections within the junction box.
a. Connect supply ground lead to luminaire
ground, bare/tinned wire.
b. Connect the white/red luminaire lead
to the supply switched hot.
c. Connect supply line conductor to luminaire hot (black).
d. Connect supply neutral conductor to luminaire neutral (white).
STEP 3:
Once ITS is installed make the following electrical
connections within the junction box:
a. Connect ITS violet lead to luminaire’s lead.
b. Connect ITS brown lead to luminaire’s brown - lead.
STEP 4:
Locate the two red leads coming off of the Emergency Driver and
connect them using supplied connector. See
Figure 1 on page 1.
HOT
GROUND
BLACK
BARE/TINNED
WHITE
NEUTRAL
SUPPL
Y WIRING
LUMINAIRE
JUNCTION BOX
VIOLET
BROWN -
BROWN