background image

HazFlood DFL
Floodlight 150 - 400 Watts

Installation & Maintenance Information

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

IF 1620

APPLICATION

HazFlood DFL nR Series Floodlights are suitable for use in the following
hazardous (classified) locations as defined by the National Electrical
Code (NEC

®

), Canadian Electrical Code (CEC), and International

Electrotechnical Commission (IEC):

Class I, Division 2, Groups A, B, C, D; Class I, Zone 2 IIC  

Class I, Zone 2, AEx nR, (AEx nA nR with outlet box) Group IIC

IEC Zone 2, Ex nR IIC

Type “n” protection is defined in IEC 60079-15 as “A type of protection
applied to electrical apparatus such that, in normal operation, the
electrical apparatus is not capable of igniting a surrounding explosive
gas atmosphere and a fault capable of causing ignition is not likely to
occur.”

This luminaire is a restricted breathing product.  Restricted breathing,
identified by the marking “Ex nR” (AEx nR in the U.S.) means that an
enclosure is sufficiently well sealed to limit the entry of flammable gas to
below explosive concentration.

The HazFlood DFL nR Series Floodlight comes standard as a “restricted

breathing” luminaire.  That means it restricts vapors and gases from
entering inside the luminaire.  Therefore, please retain and use the
sealing cord connector (located on the bottom right corner of the
luminaire) with 16-3 type SOW or equal cord.

Refer to the floodlight nameplate for specific classification information,
maximum ambient temperature suitability, and corresponding operating
temperature (T-Number).                                     

HazFlood DFL nR Series Floodlight Type 4X / IP66 construction is
designed for use indoors and outdoors in marine and wet locations,
where moisture, dirt, corrosion, vibration and rough usage may be
present.  

HazFlood DFL nR Series Floodlights are supplied for use with a choice
of voltages (120, 208, 220, 240, 277, 480, tri-tap, multi-tap, etc.),
frequencies (50 Hz or 60 Hz), and light sources (High Pressure Sodium-
HPS, Metal Halide-MH) in ratings of 150 through 400 watts.

WARNING

To avoid the risk of fire, explosion, or electric shock

, this

product should be installed, inspected, and maintained by a
qualified electrician only, in accordance with all applicable electrical
codes.

WARNING

To avoid electric shock

:

Be certain electrical power is OFF before and during installation and
maintenance.

Floodlight must be supplied by a wiring system with an
equipment grounding conductor.

To avoid burning hands:

Be sure line power to the ballast assembly is OFF for at least 15
minutes to allow the capacitor to discharge.

Make sure lens and lamp are cool when performing maintenance.

To avoid explosion: 

Make sure the supply voltage is the same as the floodlight voltage.

Do not install where the marked operating temperatures exceed the
ignition temperature of the hazardous atmosphere.

Do not operate in ambient temperatures above those indicated on the
floodlight nameplate.

Do not position the floodlight beyond the aiming range limits depicted
on page 4.  

Use only the lamp and wattage specified on the floodlight nameplate.

Use proper supply wiring as specified on the floodlight nameplate.

All gasket seals must be clean.

Before opening, electrical power to the floodlight must be turned off.
Keep tightly closed when in operation.

To maintain restricted breathing properties do not substitute cable
fitting supplied with fixture.

IF 1620  •  03/11

Copyright © 2011, Cooper Industries, Inc.

Page 1

INSTALLATION

Mounting

A)  Pole Mount with SFA6 Slipfitter

1.

Using the two 

1

2

" mounting bolts, nuts, and lock washers provided,

securely fasten the floodlight yoke to the flange on the SFA6
slipfitter. See Figure 1. Torque the bolts to 45 lbs.-ft. 

NOTE

: Angular positioning of the floodlight will be done later.

2.

Place the SFA6 slipfitter adapter with the secured floodlight onto the
2" Pole top tenon.

3.

Secure by tightening the slipfitter base bolts. Torque base bolts to
19 lbs.-ft.

SFA6 FLANGE

YOKE ARM

(4) BASE BOLTS

(2) MOUNTING

   BOLTS

Figure 1 - SFA6

WARNING

Summary of Contents for Paulihn hazFlood DFL Series

Page 1: ...Hz or 60 Hz and light sources High Pressure Sodium HPS Metal Halide MH in ratings of 150 through 400 watts WARNING To avoid the risk of fire explosion or electric shock this product should be installed inspected and maintained by a qualified electrician only in accordance with all applicable electrical codes WARNING To avoid electric shock Be certain electrical power is OFF before and during insta...

Page 2: ...portable cord or other extra hard usage portable cord into the GRFX outlet box using a Crouse Hinds NCG75 75 cable connector See Figure 5 The cord length required will allow ample slack to adjust the aiming angle of the floodlight Figure 3 Pole Mount with SFA6 Slipfitter CGB294SA 16 3 Type SOW Cord Figure 4 GASK643 GRF10SA S752 GRFX229 S752 Figure 5 Wall Mount with Outlet Box 16 3 Type SOW Cord NC...

Page 3: ...wer on LAMP INSTALLATION REPLACEMENT 1 Note both vertical and radial aiming angles If these are disturbed during relamping they should be readjusted after relamping 2 Disconnect power to the floodlight and allow to cool completely Allow the capacitor to discharge for 15 minutes 3 Completely loosen the 6 captive cover screws and swing open the cover See Figure 7 4 Remove lamp 5 Perform cleaning and...

Page 4: ...k to make sure that all connections are clean and tight Mechanically check that all parts are properly assembled REPLACEMENT PARTS Cooper Crouse Hinds Pauluhn HazFlood DFL nR Series Floodlights are designed to provide years of reliable lighting performance However should the need for replacement parts arise they are available through your authorized Cooper Crouse Hinds Pauluhn distributor Assistan...

Reviews: