Crane Deming 7360 Series Installation, Operation & Maintenance Manual Download Page 8

8

MOISTURE SENSING RELAY

Moisture sensing replay is a conductance actuated control 
for detecting moisture in the oil chamber of a submersible 
motor. It is used as a warning device to indicate a 
seal leakage and to signal the need for preventive 
maintenance.

Mount the control box vertically on a wall or other solid 
structure and complete all indicated wiring as shown 
on the above wiring diagram. Terminals on the control 
are numbered, as shown Terminal Pair I and 2 must be 
continuously energized from an AC supply line of the correct 
voltage as shown on the control data plate. Contacts 5 and 
6 or 7 and 8 are available for connecting audible alarm 
or light if required and must be wired in series with such 
device; and that series branch circuit connected across the 
power source compatible with the load. Terminals 9 and 10 
are connected to the moisture sensing probe in the motors 
marked WI and W2 by means of the cable provided with 
the motor. See Figure 5.

OPERATION

Normally the oil surrounding the probes is non-conductive 
and the control and seal leakage indicator light will be de-
energized. An infl ux of moisture past the outer seal and into 
the oil reservoir will change the conductivity of the oil and 
this condition will cause the relay to energize and the seal 
leakage light and/or alarm will energize to indicate a seal 
leakage. Load contacts 5 and 6 or 7 and 8 will also change 
from their normally open position to a closed position when 
the control energizes.

TEST PROCEDURES

A normally closed push-button and neon indicating 
light are provided as a part of the control for testing the 
moisture sensing components. The motor manufacturer 
has provided a resistor across the probes inside the motor 
to complete the test. When the test button is depressed 
the neon indicating lamp and alarm if installed will be 
activated to indicate: 
  A) Power is supplied to the control; 
  B) Control is operative; 
  C) The wiring to the moisture sensing probe in the 
       motor is intact.

This check does not stimulate a seal leakage, but indicates 
that the circuit is operative should a leak occur. 

Caution: The voltage will be present at all terminals on 
the control when this test is being made.

LIQUID LEVEL CONTROL SYSTEM

A liquid level control system, to automatically start and 
stop the pump(s), such as fl oat switch, mercury switches, 
such as Deming Fig. 1601, or electrode probes with proper 
relay must be installed with the pump. The actuating switch 
for such controls is connected in the control circuit of the 
magnetic starter.

Liquid level controls must be adjusted to stop the motor if 
liquid level in the sump lowers to a point uncovering the 
motor. If sump is to be drained—that is, motor uncovered— 
some means, such as an automatic timing device, must 
be used to limit uncovered operation to 10 minutes with 
suffi cient time allowed for cooling of the motor before 
restarting.

STARTING

On the initial start-up, the motor and pump must be 
checked for proper rotation prior to fi nal installation. See 
section on “Direction of Rotation”. The motor should under 
no conditions be operated for any appreciable length of 
time unless submerged in the liquid as indicated above.

OPERATION

After the pump is in position, discharge piping has been 
completed and all electrical connections made, the unit 
may be started as follow’s:

1. 

Adjust liquid level controls. Make certain that the

 

controls will stop the pump when the liquid level

 

reaches the level shown on the Dimension Print on

 

Page 3. This minimum level is for continuous 

 

operation and results in the motor being completely

 

submerged at all times.

2. 

Open discharge valve, if used.

3. 

Allow liquid to enter sump or pit.

4. 

Energize motor, either by automatic control device or

 manually.

5. 

Check liquid level operation as described in Step #1.

Figure 5

Summary of Contents for Deming 7360 Series

Page 1: ...mps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 120030 Rev E Series 7360 Section 42 DEMING DEMING INSTALLATION OPERATION MAINTENANCE MANUAL Demersible Solids Handling Wet Pit Pumps Manua...

Page 2: ...MENSIONS 4 GENERAL INFORMATION 5 Application 5 Receiving 5 Storage 5 Service Centers 5 Power Supply 5 Equipment 5 Motors 5 Direction of Rotation 6 Foundation 6 Piping 6 Installation 6 Three Phase 6 Single Phase 7 Moistur Sensing Relay 8 Operation 8 Test Procedures 8 Liquid Level Control System 8 Starting 8 Operation 8 GENERAL MAINTENANCE 9 Disassembly Reassembly LOCATING TROUBLE 9 CROSS SECTION PA...

Page 3: ...gs DO NOT insert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Secure the pump in its operating position so it can not tip over fall or slide DO NOT exceed m...

Page 4: ...00 3 433 EB180TY 34 63 12 13 3 25 19 63 12 25 6 25 6 25 6 25 4 00 27 63 10 50 435 EB210TY 40 38 21 00 15 25 7 63 7 63 7 63 32 25 437 EB180TY 34 88 12 75 20 50 14 38 7 75 6 63 7 13 27 88 EB210TY 41 38 21 00 15 38 7 63 7 63 33 25 438 EB210TY 39 88 21 50 31 75 11 00 Fig 7360 Pumps with Tandem Seal Submersible Motors SUBMERSIBLE MOTOR FRAMES HP THREE PHASE SINGLE PHASE 1750RPM 1150RPM 1750RPM 1150RPM ...

Page 5: ...ercent and at a voltage not more than 10 percent above or below the nameplate rating Performance within this range will not necessarily be the same as the established performance at the correct rated voltage and frequency EQUIPMENT Three phase units consist of the pumping unit including motor with waterproof power cable and control cable the liquid end with discharge flange and moisture sensing re...

Page 6: ...cessive reverse flow on the pump shutdown can cause cycling of the pump Brief reverse rotation is not damaging to the pump providing the pump does not restart when running in reverse rotation INSTALLATION Lowering Unit into Sump or Pit Lifting eyes are supplied on top of the motor frame for the purpose of lowering raising the unit when making installation servicing the unit Caution Do not use disc...

Page 7: ...r B Motor Refer to motor description and cable identification on Page 4 Connect the three power leads of the power cable to the motor control box and the ground wire to ground install and connect power leads from the motor control box to the starter 1 Connect the two leads marked P1 and P2 of the control cable to the CONTROL CIRCUIT of the starter See Wiring diagrams Figures 3 4 C Liquid Level Con...

Page 8: ...ating lamp and alarm if installed will be activated to indicate A Power is supplied to the control B Control is operative C The wiring to the moisture sensing probe in the motor is intact This check does not stimulate a seal leakage but indicates that the circuit is operative should a leak occur Caution The voltage will be present at all terminals on the control when this test is being made LIQUID...

Page 9: ... clearance av 030 E Insert motor screws 212 and tighten down after proper impeller clearance has been established Motor Repair Should it become necessary to replace seals or bearings or make repairs to the motor please contact the nearest office of Reliance Electric Company for address of Authorized Service Station in your area See Motor Warranty Motor Warranty The submersible type motor furnished...

Page 10: ...tor 24 Impeller Washer 26 Impeller Screw 32 Impeller Key 71 Motor Adapter 73 Motor Gasket 104 Cap Screws ITEM No DESCRIPTION 107 Discharge Gasket 161 Discharge Flange 212 Capscrew or Stud 219 Capscrew or Stud 294 Impeller Shim Recommended Spare Parts ...

Page 11: ...formance specifications must be in writing and such writing must be signed by our authorized representative Due to inaccuracies in field testing if a conflict arises between the results of field testing conducted by or for user and laboratory tests corrected for field performance the latter shall control RECOMMENDATIONS FOR SPECIAL APPLICATIONS OR THOSE RESULTING FROM SYSTEMS ANALYSES AND EVALUATI...

Page 12: ...nt To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration Form go to http www cranepumps com ProductRegistration If you have a claim under the provision of the warranty contact your local Crane Pumps...

Page 13: ...__ Type _________________________________ Number and size of short circuit device s ___________ Amp rating ___________________ Overload Type _____________ Size ______________ Amp rating ___________________ Do protection devices comply with pump and motor Amp rating YES___ NO___ Are all electrical and panel entry connections tight YES___ NO___ Is the interior of the panel dry YES___ NO___ Liquid le...

Page 14: ...s installed away from turbulence YES___ NO___ Is level control operating properly YES___ NO___ Is pump fully submerged during operation YES___ NO___ Follow up Corrective Action Required YES___ NO___ Additional Comments ____________________________________________________________________________ ____________________________________________________________________________ ___________________________...

Reviews: