10
MODEL
NO
HP
V
O
LT
PH
Hz
RPM (Nom)
NEMA ST
AR
T
CODE
FULL LOA
D
AMPS
SER
VICE
FA
CT
OR
SER
VICE
FA
CT
OR
AMPS
LOCKED R
O
T
OR
AMPS
CORD P/N
▲
CORD SIZE
CORD O.
D
.
WINDING
RESIST
ANCE
SITHE SCDU Pump
8SCDU25094
25.0
208
3
60
1750
G
77.8
1.2
93.4
359.0
138319
2/4 - 18/4
1.47 ± .03
.098
230
71.4
82.3
8SCDU30094
30.0
208
3
60
1750
E
93.4
1.2
116.9
359.0
138319
2/4 - 18/4
1.47 ± .03
.098
230
82.3
1.2
98.7
8SCDU40034
40.0
230
3
60
1750
E
106.0
1.2
126.4
486.0
138319
2/4 - 18/4
1.47 ± .03
.063
8SCDU40044
40.0
460
3
60
1750
E
53.0
1.2
63.2
243.0
138318
6/4 - 18/4
1.14 ± .03
.248
8SCDU40054
40.0
575
3
60
1750
E
42.4
1.2
50.6
194.4
138317
8/4 - 18/4
1.12 ± .02
.382
8SCDU50044
50.0
460
3
60
1750
F
67.1
1.2
79.0
339.0
138318
6/4 - 18/4
1.14 ± .03
.15
8SCDU50054
50.0
575
3
60
1750
F
53.7
1.2
63.2
271.2
138318
6/4 - 18/4
1.14 ± .03
.245
8SCDU60044
60.0
460
3
60
1750
E
79.0
1.2
95.5
339.0
138319
2/4 - 18/4
1.47 ± .03
.15
8SCDU60054
60.0
575
3
60
1750
E
63.2
1.2
76.4
271.2
138318
6/4 - 18/4
1.14 ± .03
.245
8SCDU20096
20.0
208
3
60
1150
H
60.3
1.2
71.5
354.0
138318
6/4 - 18/4
1.14 ± .03
.111
7
230
57.2
1.2
69.8
8SCDU25096
25.0
208
3
60
1150
G
75.2
1.2
90.8
354.0
138319
2/4 - 18/4
1.47 ± .03
.111
7
230
70.8
1.2
82.6
8SCDU25046
25.0
460
3
60
1150
G
35.4
1.2
41.3
177.0
138317
8/4 - 18/4
1.12 ± .02
.4397
8SCDU25056
25.0
575
3
60
1150
G
28.3
1.2
33.0
141.6
138317
8/4 - 18/4
1.12 ± .02
.6857
8SCDU7598
7.5
208
3
60
870
L
32.0
1.2
35.0
230.0
138317
8/4 - 18/4
1.12 ± .02
.199
230
34.6
36.9
8SCDU7548
7.5
460
3
60
870
L
17.3
1.2
18.5
115.0
138317
8/4 - 18/4
1.12 ± .02
.795
8SCDU7658
7.5
575
3
60
870
L
13.9
1.2
14.8
92.0
138317
8/4 - 18/4
1.12 ± .02
1.27
8SCDU10098
10.0
208
3
60
870
L
37.2
1.2
42.0
230.0
138317
8/4 - 18/4
1.12 ± .02
.199
230
38.6
42.2
8SCDU10048
10.0
460
3
60
870
L
19.3
1.2
21.1
115.0
138317
8/4 - 18/4
1.12 ± .02
.795
8SCDU10058
10.0
575
3
60
870
L
15.4
1.2
16.9
92.0
138317
8/4 - 18/4
1.12 ± .02
1.27
8SCDU15098
15.0
208
3
60
870
G
50.4
1.2
59.0
230.0
138317
8/4 - 18/4
1.12 ± .02
.199
230
48.4
55.6
8SCDU15048
15.0
460
3
60
870
G
24.2
1.2
27.8
115.0
138317
8/4 - 18/4
1.12 ± .02
.795
8SCDU15058
15.0
575
3
60
870
G
19.4
1.2
22.2
92.0
138317
8/4 - 18/4
1.12 ± .02
1.27
Moisture and
Temperature sensor leads are integral to power cord.
Winding Resistance ± 7.5%
Winding resistance measured in OHMS @ 25°C (Between Lines) at motor leads.
Pump rated for operation at ± 10% voltage at motor
.
▲ Cord Suffix: XF - 50 Feet, XJ - 75 Feet, or XL
- 100 Feet
▲ Cord sold separately
.
CHART ‘E’