ELECTRICAL CONNECTIONS:
Pump Cord -
The cord assembly mounted to the pump
must
NOT
be modified in any way except for shortening
to a specific application. Any supply cables connection
between the pump and the control panel must be made
in accordance with the National Electric Code or the
Canadian Electric Code and all applicable state, province
and local electric codes. It is recommended that a junction
box, be mounted outside the sump or be of at least Nema
4 (EEMAC-4) construction if located within the wet well.
DO NOT USE THE POWER OR CONTROL CABLES TO
LIFT PUMP!
Overload Protection -
The type of in-winding overload
protector used is referred to as an inherent overheating
protector and operates on the combined effect of
temperature and current. This means that the overload
protector will trip out and shut the pump off if the windings
become too hot, or the load current becomes too high.
It will then automatically reset and start the pump after
the motor cools to a safe temperature. In the event
of an overload, the source of this condition should be
determined and rectified immediately.
DO NOT LET THE
PUMP CYCLE OR RUN IF AN OVERLOAD CONDITION
OCCURS !
Wire Size -
If additional cord is required consult a qualified
electrician for proper wire size.
CORD CONNECTIONS:
Power/Control Cord-
Insert female end of cord plug into
housing bore aligning alignment mark with hole in terminal
block see Figure 4. Tighten bolts on compression flange
until flush with motor housing.
FIGURE 4
FIGURE 5