- 21 -
OPERATION
4.2.3.2 - Procedure for modifying the parameters of the parallel shift of the heating curve
4.2.3.3 - Return to the initial display
1
Initial display: Green LED “°C” is on
The display shows the heating flow temperature.
2
Press the
key until
is displayed then release it and press for the same period until
is
displayed (the display indicates
then
: intermediary positions)
3
After a few moments,
is displayed.
4
Press on the
key three times until
is displayed on the screen.
5
setting of the parallel shift permutes with
the default value of the shift.
6
Only when the display shows
press the
key until the “bar” LED flashes:
7
Increase the value
by pressing
until the value
is displayed.
8
Store the value
by pressing the
key for a certain time until the LEDS “°C” and “bar”
extinguish
9
Return to the initial display
bar
Info
°C
INFO
-2
2
Info
Info
Info
bar
Info
°C
IN
FO-
15c
Info
Info
bar
Info
°C
IN
F
O
-8
Procedure
Observation
Press the
key until the
display appears
then release the key.
This enables you to return to the initial position (i.e. the
display shows the heating flow temperature) when the
procedures 4.2.3.1 - page 20 and 4.2.3.2 - page 21 are
being applied or during any other actions on the boiler
control panel.