13
3.3 Mounting the PV-Inverter
To mount the inverter to a wall or structure, please follow these steps:
1.
Select a wall or solid vertical surface which is strong enough to support
the inverter.
2.
The PV-Inverter requires adequate cooling space for heat dissipation.
Reserve at least 300mm
(~12”) above and 500mm (~20”) (measured
start from the bottom of the AC cover) below the inverter. Each
inverter should have a minimum of 300mm
(~12”) space to each other
for multiple inverters installation.
INSTRUCTION:
The PV-Inverter can operate at locations where the ambient temperature
is up to 60
C (140
F). However, for optimal power production, it is
recommended that inverter is installed where the ambient temperature is
between -25
C and +45
C (-13
F ~+113
F)