background image

Using the

 Leak-Seeker

 

®

 

I

SMART-BUTTON Operation:
• Press the START button to turn the instrument ON.
• While in any mode, press and hold the START button for three 

seconds to turn the instrument OFF.

• Press and hold the START button to change sensitivity 

settings. The corresponding LED will turn on to indicate the 

sensitivity setting.

• Click the START button to reset the Leak-Seeker

®

 

I

 to the 

ambient contamination level.

• Double-click the START button to silence the audible alarm. 

Double-click again to restore the audible alarm.

Mode and Sensitivity Selection:
The Leak-Seeker 

®

 

I

 offers two modes of opertion. The Progressive 

Alarm Mode should be used to guide the user to the source leak; the 

pitch of the alarm and the number of LED's increases progressively 

as the leak source is approached. The Progressive Alarm allows 

searching for a broad range of leak sizes, and the searching should 

be started in the large leak setting (L) since those leaks need to be 

fixed first. If you start in the highest sensitivity setting, the alarm 

may saturate far away from the actual leak and then you would 

have to back to a lower sensitivity setting.

The Threshold Alarm Mode provides a quick go or no go mode 

to  verify  that  a  leak  has  been  found  and  its  approximate  size. 

Always scan the suspected leak site several times to make sure 

you are detecting a leak and not accumulated refrigerant.

Low battery indicator 

 :

When  the  batteries  reach  approximately  10%  of  capacity,  the 

GREEN LED turns OFF.

Windy conditions: 
Locating leaks under windy conditions may severely impede the 

leak searching process. Even very large leaks may be difficult to 

locate as the escaping gas is quickly dissipated into the atmo-

sphere.  If  necessary,  fabricate  a  gas  trap  using  aluminum  foil 

around joints or fittings or otherwise shield the search area from 

the wind.

Leak verification:
If a suspected leak is indicated, verify several times by moving 

the sensor away from the leak area, resetting the unit and then 

back  to  the  suspected  leak.  If  the  instrument  indicates  a  leak 

three consecutive times, then you have found a leak.

6

OPERATION

Summary of Contents for Leak-Seeker 1

Page 1: ...Leak Seeker I Refrigerant Leak Detector CE US Patent8 555 701 OPERATION MANUAL Test Equipment Depot 800 517 8431 99 Washington Street Melrose MA 02176 TestEquipmentDepot com ...

Page 2: ... Introduction GENERAL INFORMATION Smart Button operation for ON OFF mode setting signal reset and audible alarm ON OFF Progressive alarm settings for Large L Medium M and Small S leak searching Flexible metal probe 15 380mm long 25 6 4mm diameter High output alarm speaker Bar graph indicator displays relative leak size Threshold Alarm settings for precise Large Medium and Small leak detection Sens...

Page 3: ...uble clicking the START button Eight LED bar graph indication signaling the relative size of the leak in the Progressive Alarm mode Solid 8 LED bar turns on in the Threshold Alarm mode when a leak is present Operating Temperature 18 to 60 C 0 to 140 F Power Three size C alkaline batteries NEDA ANSI 14A Battery Life 50 hours minimum at 77 F 25 C Battery life depends on cell chemistry and ambi ent c...

Page 4: ... eliminates false alarms due to the presence of conden sate Operation of this advanced instrument is fully controlled by a single SMART BUTTON switch Microprocessor controlled sensor electronics utilizing a multi channel signal detection method improves sensitivity while reducing false alarms New E_MOS sensor technology incorporates a proprietary pulse modulation design to increase both battery an...

Page 5: ...ximately 0 5 oz year 14 g yr Small Leak Setting S Alarm saturates at approximately 0 125 oz year 4 g yr leak rate Threshold Alarm Mode The audible alarm sounds a low pitch tone interrupted twice per second until a given leak rate is found When the leak is found the audible alarm sounds a high pitch tone and all the LED in the bar graph turn on at once Three white LED s indicate the current setting...

Page 6: ... to be fixed first If you start in the highest sensitivity setting the alarm may saturate far away from the actual leak and then you would have to back to a lower sensitivity setting The Threshold Alarm Mode provides a quick go or no go mode to verify that a leak has been found and its approximate size Always scan the suspected leak site several times to make sure you are detecting a leak and not ...

Page 7: ...gerant system around in a continuous path so that no areas of potential leaks are missed If a leak is found always continue to test the remainder of the system 3 At each area checked the probe should be moved around the location at a rate no more than 1 2 in sec 25 to 50mm sec and no more than 2 5mm from the surface completely around the position Slower and closer movement of the probe greatly imp...

Page 8: ......

Page 9: ......

Page 10: ...ntee does not apply to equipment that has been altered misused or returned solely in need of field service maintenance This repair policy does not include equipment that is determined to be beyond economical repair All products being returned for warranty repair must be accompanied by an original bill of sale and customer contact information 10 WARRANTY Test Equipment Depot 800 517 8431 99 Washing...

Reviews: