WATER DISTRIBUTION
Pressure
Bar
Real Press
Bar
Discharge
l/min
K Factor
0,69
0,71
68,5
80,35
1,38
1,38
96,9
81,35
2,07
2,07
114
77,8
2,76
2,78
137
81,35
3,45
3,5
154,4
81,78
4,14
4,13
166,5
81,2
4,83
4,84
180
81,06
5,52
5,54
192
80,64
80,69
K
FA
C
TO
R
I D
IS
C
H
A
R
G
E.
LEGENDA COLORI BULBI SPRINKLER
BULBS COLOR
I dati riportati nelle tabelle e diagrammi presenti sul presente opuscolo
sono tratti da test realmente effettuati da ente di parte terza
Data showing in the present diagrams are been
deduced from really tests effected by
TIPO
TYPE
TEMPERRATURA
TEMPERATURE
COLORE
COLOR
G5-F3
57°C = 135°F
Arancio / Orange
G5-F3
68°C = 155°F
Rosso / Red
G5-F3
79°C = 175°F
Giallo / Yellow
G5-F3
93°C = 200°F
Verde / Green
G5-F3
141°C = 286°F
Blu / Blue
G5-F3
182°C = 360°F
Malva / MaUVE