Choosing a Suitable Location 

The EBDSPIR-AD is designed to be ceiling mounted and must satisfy the following criteria: 

 

Avoid positioning the unit where direct sunlight may enter the sensor element.  

 

Do not site the sensor within 1m of any lighting, forced air heating or ventilation. 

 

Do not fix the sensor to an unstable or vibrating surface. 

 
 

Installation 

Detection Mode 

The Detection Mode for both output Channels 1 and 2 can be set to behave in Presence or Absence mode: 

 

Presence

 When movement is detected the load will automatically turn on. When the area is no longer occupied the 

load will automatically switch off after an adjustable time period.  

 

Absence 

The load is manually switched on. When the area is no longer occupied the load will automatically switch 

off after the adjustable time period has elapsed.  

In either case, sensitivity to movement of the PIR sensor  can be adjusted using the Sensitivity parameter. 

HINT: To assist in setting the Sensitivity, turn on the Walk Test LED which will flash red when movement is detected. 

 
Switch Level On/Off 

Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level 
parameters. 

 

 
 
 
 
 
 
 
 
 
 
 
 

Maintained Illuminance (daylight harvesting) 

The detector measures the overall light level in the detection area and calculates the correct output for the luminaires, to 
achieve a preset lux level (maintained illuminance or daylight harvesting).  

Sensor functionality  

Overview 

It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of time 
to guarantee lamp life (refer to the manufacturer’s datasheet for details) As this EBDSPIR-AD is able to dim the lamps 
using 1-10V, the product provides a facility to disable this for a given period of time. 

Operation 

By setting the “Burn in” parameter, you can select a time during which the lamps are not allowed to deviate from 
maximum output. The unit counts the time, and even remembers how long has elapsed in the event of a power failure. 
To cancel the burn in function, simply select a time of 0. Note that when the lamps are changed, the burn in time should 
be set again. 

Burn-in 

Summary of Contents for EBDSPIR-AD

Page 1: ...ontrol Output Connector Channel 2 Switch Input Connector PIR Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor Measures the overall light level in the detection area Status LEDs The LED flashes Red to indicate the following Power Inp...

Page 2: ...2 Detection diagram Area of lower sensitivity Area of high sensitivity ...

Page 3: ... Walk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters Maintained Illuminance daylight harvesting The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to achieve a preset lux level mai...

Page 4: ...than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Notes If a parameter s has been missed because of a communication error the missing value s is replaced by dashes When reading back the Channel 1 ...

Page 5: ...L OUT L N SW1 UP SW2 DOWN DIMMING BALLAST DIMMING LUMINAIRE 1 10V CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection L OUT L N SW1 UP SW2 DOWN CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection LUMINAIRE NON DIMM...

Page 6: ...f Turns off after occupancy Channel mode Set to Switch only Switch mode Set to 2 position switch together Note a single position switch can be used instead to toggle the output set to 1 position switch separate L OUT L N SW1 UP SW2 DOWN DIMMING BALLAST DIMMING LUMINAIRE 1 10V CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory ...

Page 7: ...ircuit is good Check that the load is functioning by bypassing the sensor e g link terminals L and L Out on Channel1 If the detection range is smaller than expected check the diagram on page 2 Rotating the sensor slightly may improve the detection range HINT The Walk Test LED function can be used to check that the unit is detecting movement in the required area What if the load does not turn OFF E...

Page 8: ...ux On Level value Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit to the default settings Burn in 0 0 50 100 Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Presence Absence Presence Presence Absence Presence mode allows the output t...

Page 9: ...ght they will turn off again after the Lux Time Note that whenever the an external switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or Off Select No for a 30 second delay on start up If Yes is selected there will be no delay on start up and the detector will ...

Page 10: ...Maximum dimming output level Min Value 0 0 to 100 Minimum dimming output level Memorise N Yes or No If this is set to Yes the last manual lux level set will be memorised and used as the new switch on level On value 99 0 to 99 Dimming output level when switched on 0 99 Off value 0 0 to 99 Dimming output level when switched off 0 99 If a non zero off value is set then the output will toggle between ...

Page 11: ...11 This page intentionally left blank ...

Page 12: ...35ºC Humidity 5 to 95 non condensing Material casing Flame retardant ABS and PC ABS Type Class 2 IP rating EBDSPIR AD IP40 EBDSPIR AD IP IP55 EBDSPIR AD IP LT30 IP55 Compliance EMC 2004 108 EC LVD 2006 95 EC Technical data Part numbers C P Electronics Ltd Brent Crescent London NW10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Re...

Reviews: