background image

12  

 

Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice. 

Dimensions 

See diagrams opposite 

Weight 

0.15kg 

Supply Voltage 

/- 10%  

Frequency 

50Hz 

Maximum Load 

Channel 1 (switching):

 

10A of lighting and/or ventilation 

including incandescent, fluorescent, 
compact fluorescent, low voltage (by 
switching the primary of transformer). 

Channel 2 (dimming): 

Maximum number of 1-10V 
ballasts is 10. 

Power consumption 

On 724mW, Off 260mW 

 
Dimming output 

Basic insulation only. Although low 
voltage, this is not an SELV output 
and should be treated as if mains 
potential. Use mains rated wiring. 

Terminal Capacity 

2.5mm

2

 

Temperature 

EBDSPIR-AD  

-10ºC to 35ºC 

 

EBDSPIR-AD-IP 

-10ºC to 35ºC 

 

EBDSPIR-AD-IP-LT30 -30ºC to 35ºC 

Humidity 

5 to 95% non-condensing 

Material (casing) 

Flame retardant ABS and PC/ABS 

Type 

Class 2 

IP rating 

EBDSPIR-AD  

 

IP40 

 

EBDSPIR-AD-IP 

 

IP55 

 

EBDSPIR-AD-IP-LT30 

IP55 

 
Compliance 

EMC-2004/108/EC 
LVD-2006/95/EC 

Technical data 

Part numbers 

C.P. Electronics Ltd

 

Brent Crescent 
London 
NW10 7XR 
United Kingdom 
Tel: 

+ 44 (0) 333 900 0671 

Fax: 

+ 44 (0) 333 900 0674 

www.cpelectronics.co.uk 
[email protected] 

Ref:  #WD485    Issue 4 

FM 45789 

EMS 534520 

IMPORTANT NOTICE! 

This device should be installed by a qualified electrician in 
accordance with the latest edition of the IEE Wiring 
Regulations and any applicable Building Regulations. 

EBDSPIR-AD 

DBB 

 

Part number 

Description 

Detector 

EBDSPIR-AD 

Ceiling PIR presence detector – 1-10V dimming 

 

EBDSPIR-AD-IP 

Ceiling PIR presence detector – 1-10V dimming sealed to IP55 

 

EBDSPIR-AD-IP-LT30 Ceiling PIR presence detector – 1-10V dimming sealed to IP55 -30ºC 

Accessories 

DBB 

Surface mounting box 

 

UHS5 

Programming IR handset 

 

UNLCDHS 

Universal LCD IR handset 

Summary of Contents for EBDSPIR-AD

Page 1: ...ontrol Output Connector Channel 2 Switch Input Connector PIR Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor Measures the overall light level in the detection area Status LEDs The LED flashes Red to indicate the following Power Inp...

Page 2: ...2 Detection diagram Area of lower sensitivity Area of high sensitivity ...

Page 3: ... Walk Test LED which will flash red when movement is detected Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters Maintained Illuminance daylight harvesting The detector measures the overall light level in the detection area and calculates the correct output for the luminaires to achieve a preset lux level mai...

Page 4: ...than 1 second The handset will click every time a parameter is received The device will show multiple flashes of its LED All of the values will be shown against the parameters in the menu The individual parameters may be edited and then saved as a Macro Notes If a parameter s has been missed because of a communication error the missing value s is replaced by dashes When reading back the Channel 1 ...

Page 5: ...L OUT L N SW1 UP SW2 DOWN DIMMING BALLAST DIMMING LUMINAIRE 1 10V CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection L OUT L N SW1 UP SW2 DOWN CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory for absence detection LUMINAIRE NON DIMM...

Page 6: ...f Turns off after occupancy Channel mode Set to Switch only Switch mode Set to 2 position switch together Note a single position switch can be used instead to toggle the output set to 1 position switch separate L OUT L N SW1 UP SW2 DOWN DIMMING BALLAST DIMMING LUMINAIRE 1 10V CIRCUIT PROTECTION IF REQUIRED LIVE NEUTRAL CENTRE BIASED RETRACTIVE SWITCH 240V SWITCHING Optional for presence mandatory ...

Page 7: ...ircuit is good Check that the load is functioning by bypassing the sensor e g link terminals L and L Out on Channel1 If the detection range is smaller than expected check the diagram on page 2 Rotating the sensor slightly may improve the detection range HINT The Walk Test LED function can be used to check that the unit is detecting movement in the required area What if the load does not turn OFF E...

Page 8: ...ux On Level value Sensitivity 9 1 5 9 3 6 8 Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Defaults D Returns the unit to the default settings Burn in 0 0 50 100 Determines how long the output will be at 100 so that lamps burn in The burn in time is not affected by power supply interruptions Presence Absence Presence Presence Absence Presence mode allows the output t...

Page 9: ...ght they will turn off again after the Lux Time Note that whenever the an external switch is pressed whether in absence or presence mode if the lights were out because of the lux level they will be immediately turned on again for at least the Lux Time Power Up State On On or Off Select No for a 30 second delay on start up If Yes is selected there will be no delay on start up and the detector will ...

Page 10: ...Maximum dimming output level Min Value 0 0 to 100 Minimum dimming output level Memorise N Yes or No If this is set to Yes the last manual lux level set will be memorised and used as the new switch on level On value 99 0 to 99 Dimming output level when switched on 0 99 Off value 0 0 to 99 Dimming output level when switched off 0 99 If a non zero off value is set then the output will toggle between ...

Page 11: ...11 This page intentionally left blank ...

Page 12: ...35ºC Humidity 5 to 95 non condensing Material casing Flame retardant ABS and PC ABS Type Class 2 IP rating EBDSPIR AD IP40 EBDSPIR AD IP IP55 EBDSPIR AD IP LT30 IP55 Compliance EMC 2004 108 EC LVD 2006 95 EC Technical data Part numbers C P Electronics Ltd Brent Crescent London NW10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Re...

Reviews: