Page 4: ...hium Ion Gel AGM Lead Acid etc Suitable charging voltage from 1V 60V NOTE Please refer to Cotek AE AEK Spec sheet for the max charging current For example max charging current of AE 1500 60 is 25A but...
Page 5: ...to control the output voltage and current within supported spec and select the suitable battery type Protection Overvoltage This function is to protect the battery 3 2 COTEK SMPS Features Universal i...
Page 6: ...ng wiring p Step 1 Make sure to connect Power supply DC wire before connecting battery Step 2 Make sure to check battery spec before setting the charging voltage current Step 3 Add suitable ORingFET i...
Page 7: ...N08NS5 or equivalent Step 4 connect Battery with AE AEK power supply DC outputs be aware of reverse polarity Step 5 Install Charger Wizard to Cotek SMPS Front Panel Connection diagram as shown below p...
Page 8: ...onnect the white 24 pin connector of cable 1 to Cotek communication board CT 201 Step 7 AC Power On Step 8 Install Charger Wizard GUI to perform charging curve setting 4 2 Charger Wizard charging curv...
Page 9: ...section 4 1 Install TR Broard GUI software to set charging voltage and current 4 2 2 COTEK Charger Wizard GUI interface Connectivity and necessary equipment Please refer to section 4 1 Hardware Insta...
Page 10: ...10 A Model Name B Power Supply Rated Output Voltage and Rated Output Current C Rated Battery Voltage 2 Parameter Setting Description A B C A B C D E F G H I J L K M N O P Q R S...
Page 11: ...will also reference to the rated battery voltage selected by the operator Parameters as follow E I BULK C C Parameter Fixed charging current is G in BULK mode Conditions to enter the ABSORPTION mode...
Page 12: ...a charging pulse charge voltage is O time remain at R P S Parameter Under ABSORPTION or FLOAT when the battery voltage is lower than P and the hold time will change to BULK mode if it exceeds S 3 Func...
Page 13: ...attery is rapidly charged The current charges the batteries and gradually the voltage rises to the absorption voltage of 14 4V 12V models or 28 8V 24V models The duration of this phase depends on the...
Page 14: ...goes back to normal operation of the three step charge system User can store the charging curve set in the Charger Wizard User can use Charger Wizard tool to adjust the charging curve settings at any...
Page 15: ...FG Earth Ground Green Yellow 26 32 feet AWG 10 8 2 DC output interface 2 1 Before installation The DC cables should be as short as possible less than 6 feet 1 8 meters ideally The size of the cable sh...
Page 16: ...ginal power supply status Please make sure to power off the power supply before installing or removing the Easy Charger Wizard Warning 4 Please make sure the Easy Charger Wizard is installed in the co...
Page 17: ...tor 5 1 Failure Indicator Failure Description LED Status EEPROM checksum fail Solid Red EEPROM Null Red Slow every 3 secs Over current or Over voltage Red light twice flash every 3 secs Charging Volta...
Page 18: ...t flash four times every 3 secs power supply communication or status error Red light flash five times every 3 secs 5 2 Charging Status LED Indicator Charging status LED Status Bulk 1 Orange fast Bulk...
Page 19: ...19 Cable 1 P1 P2 Pin No Function Pin No Function Description 1 20 N C X X X 21 AUX 4 AUX 5V 0 5A or 9V 0 3A Auxiliary power 22 GND 3 GND Ground 23 RX 2 RX For RS232 Receiver function...
Page 20: ...tion service Please note that COTEK will ensure our products are operational before delivery and the warranty service is offered to the unit which has defect caused under normal use in the judgment of...