Cotech GG3300B Original Instructions Manual Download Page 9

9

EN

GL

IS

H

Connecting devices to the generator’s 230 V outlets

Note:

 

•  Only devices labelled as operating on 230 V, 50 Hz must be connected to the generator. Do not use  

the 230 V and 12 V outlets at the same time, i.e., do not run 230 V appliances whilst simultaneously 
charging a 12 V battery.

•  The generator’s rated running output wattage is 2600 W under continuous operation, and its maximum 

intermittent or surge wattage (for short bursts of extra power for starting appliances such as refrigerators)  
is 3000 W.

•  The total running wattage of the electrical devices connected to the generator should not exceed 2600 W.

1.  Make sure that all electrical devices are switched off before they are connected to the generator.
2.  Set the AC on/off switch (17) to 

ON

.

3.  Switch on the connected electrical devices in order of their wattage requirement. Begin with the device that 

requires the most power.

Note:

 The AC on/off switch also acts as an overvoltage safety cut-off switch and trips if the load of the electrical 

devices becomes too high. Reduce the load and allow the generator to rest for a while before loading it again.

12 V outlet

Note:

•  The 12 V outlet is only intended for charging lead-acid batteries (car batteries).
•  The charging current varies according to the engine speed and load. The maximum charging current is 8 A.
•  Battery charging must be supervised and discontinued manually otherwise there is a risk of the battery fluid 

boiling and damaging the battery. Whilst a battery is being charged it will emit an explosive oxyhydrogen gas 
mixture. Batteries should be charged in well-ventilated areas, and well away from sources of ignition. 

•  For more efficient car battery charging, we recommend that a 230 V AC car battery charger is connected to 

the 230 V AC outlet of the generator.

•  Do not connect batteries with capacities lower than 60 Ah.
•  The 12 V outlet is unregulated, i.e. the output voltage depends on the speed of the engine and the load on 

the generator.

•  The overvoltage safety cut-off (20) will trip if the load from the connected 12 V device becomes too high. If this 

happens, disconnect the battery and investigate the cause. Press the reset button in to reset the overvoltage 
safety cut-off protection. Allow the generator to rest for a few minutes before it is put under load again.

1.  Connect the supplied cable to the 12 V outlet socket. It can only be connected one way, so there is no risk 

of reversed polarity. 

2.  Connect the clamps to the battery terminals.
 

Note:

 Ensure that the red cable clamp is connected to the positive battery terminal and the black cable clamp 

to the negative terminal.

Switching the generator off

1.  Turn off all connected electrical devices and then unplug them from the generator.
2.  Set the AC on/off switch (17) to 

OFF

.

3.  Let the engine run for a few minutes to stabilize the temperature of the generator.
4.  Set the engine on/off switch to 

0

 

OFF

.

5.  Turn the fuel cut-off valve to 

OFF

.

Care and maintenance

•  The exterior of the generator should be cleaned using a damp cloth. Only use mild cleaning agents,  

never solvents or corrosive chemicals.

•  If the generator is not to be used for a long time, empty the fuel tank, start the generator and run it on  

the fuel remaining in the carburettor until it runs out of fuel. This ensures that the fuel does not become  
aged during storage. Petrol which has been left in the carburettor during prolonged storage can lead to 
starting problems.

Summary of Contents for GG3300B

Page 1: ...nvisningene n ye og forsikre deg om at du forst r dem f r du tar produktet i bruk Ta vare p anvisningene for seinere bruk T rke tietoa Lue n m ohjeet huolellisesti ja varmista ett olet ymm rt nyt ne e...

Page 2: ......

Page 3: ...roblems please contact our Customer Services Contents Safety 4 Buttons and functions 5 Assembly 7 Handle 7 Lower support leg 7 Wheels 7 Operating instructions 8 Preparations 8 Starting the generator 8...

Page 4: ...a building s electrical system without the help of a qualified electrician Connecting the generator in the wrong way can create feedback into the mains network resulting in an electrocution hazard Th...

Page 5: ...enerator on The air filter should be checked after every 50 hours of operation Clean if necessary Choke Closed to the left Earth spike connection Buttons and functions 1 Fuel cap 2 Fuel gauge 3 Air fi...

Page 6: ...6 ENGLISH 10 1 10 20 10 21 10 19 10 18 10 16 10 15 10 14 10 17 10 11 10 13 10 3 10 6 10 7 10 9 10 8 10 10 10 4 10 5 10 2 10 12...

Page 7: ...upport leg and then bolt the leg onto the front crossbeam Wheels Attach the wheels onto the back of the frame by passing the axle bolt through the wheels and the frame and securing them with lock nuts...

Page 8: ...oil on the dipstick add more oil until the oil level is correct 7 If there is too much oil undo one of the oil drain plugs 10 11 and drain off oil until the level is correct 8 Screw the filler cap ba...

Page 9: ...l away from sources of ignition For more efficient car battery charging we recommend that a 230 V AC car battery charger is connected to the 230 V AC outlet of the generator Do not connect batteries w...

Page 10: ...air filter Clean Spark plug Clean or change as necessary Valve clearance Have checked and adjusted by a qualified tradesman or competent person Air filter maintenance 1 Switch the generator off and l...

Page 11: ...you wiggle it a little as you pull it Note Do not pull on the cable hold the spark plug cap 3 Use the supplied spark plug wrench to unscrew the spark plug 4 Clean the electrodes and check that the ele...

Page 12: ...the overvoltage cut off has not tripped Make sure that the devices are not faulty are properly connected to the generator and that the cables are in good condition Disposal This product should be dis...

Page 13: ...essuppgifter p baksidan Inneh llsf rteckning S kerhet 14 Knappar och funktioner 15 Montering 17 Handtag 17 St dben 17 Hjul 17 Anv ndning 18 F re start 18 Start 18 Anslutning av apparater utrustning ti...

Page 14: ...t eller med en f rl ngningssladd Anslut aldrig elverket till det elektriska systemet i en byggnad utan hj lp av en beh rig elektriker Utf rs anslutningen p fel s tt kan du r ka ut f r bakstr m till el...

Page 15: ...et var 50 e driftstimme Reng r vid behov Choke St ngd till v nster Anslutning f r jordspett Knappar och funktioner 1 Tanklock 2 Br nslem tare 3 Luftfilter 4 Choke 5 T ndstift 6 Br nslekran 7 Starthand...

Page 16: ...16 SVENSKA 10 1 10 20 10 21 10 19 10 18 10 16 10 15 10 14 10 17 10 11 10 13 10 3 10 6 10 7 10 9 10 8 10 10 10 4 10 5 10 2 10 12...

Page 17: ...gummif tterna p st d benet och montera sedan st d benet p ramens fr mre tv rbalk Hjul F st hjulen i deras f sten i ramens bakre del genom att skjuta igenom hjulaxlarna och dra fast med l smuttern p f...

Page 18: ...f r mycket olja ppna en av oljeavtappningsskruvarna 10 11 och tappa ur olja tills niv n r r tt 8 Skruva tillbaka oljep fyllningspluggen Fyll p br nsle Obs Fyll endast br nsle utomhus Fyll inte nda upp...

Page 19: ...ns F r effektivare batteriladdning rekommenderas en 230 V AC laddare ansluten till 230 V AC uttaget p elverket Anslut inte batterier med kapacitet l gre n 60 Ah 12 V utg ngen r oreglerad d v s sp nnin...

Page 20: ...a Reng ring av luftfilter Reng r T ndstift Reng r eller byt vid behov Ventilspel L t auktoriserad servicepersonal eller person med tillr cklig kunskap kontrollera och justera vid behov Reng ring och b...

Page 21: ...ftet med medf ljande hylsa 4 Reng r stiftet och kontrollera elektrodavst ndet 0 7 0 8 mm L mpligt verktyg s ljs separat Skruva tillbaka t ndstiftet och s tt tillbaka t ndhatten ordentligt Br nslefilte...

Page 22: ...t inte versp nningsskydden har l st ut Kontrollera att apparaterna r felfria ordentligt anslutna till elverket och att kablarna r hela Avfallshantering N r du ska g ra dig av med produkten ska detta s...

Page 23: ...ter Se opplysninger om kundesenteret i denne bruksanvisningen Innholdsfortegnelse Sikkerhet 24 Knapper og funksjoner 25 Montering 27 H ndtak 27 St ttebein 27 Hjul 27 Bruk 28 F r start 28 Start 28 Tilk...

Page 24: ...Kobling av str mgenerator til elektrisk systemet i en bygning skal utf res av en fagl rt elektriker Hvis koblingen utf res feil kan dette i verste fall f re til skader og d dsfall Koblingene m utf re...

Page 25: ...Luftfilteret skal kontrolleres hver 50 driftstime Rengj r ved behov Choke Stengt til venstre Uttak for jordspyd Knapper og funksjoner 1 Tanklokk 2 Bensinm ler 3 Luftfilter 4 Choke 5 Tennplugg 6 Kran...

Page 26: ...26 NORSK 10 1 10 20 10 21 10 19 10 18 10 16 10 15 10 14 10 17 10 11 10 13 10 3 10 6 10 7 10 9 10 8 10 10 10 4 10 5 10 2 10 12...

Page 27: ...st ttebeina og monter deretter st ttebeinet til den fremre tverrbjelken p rammen Hjul Monter hjulene i hjulfestene p rammens bakre del Dette gj res ved skyve hjulakslene gjennom rammen og trekk til l...

Page 28: ...appeskruene 10 og 11 pnes og overfl dig olje tappes ut 8 Skru til skruen igjen P fylling av drivstoff Obs Bensin m fylles p utend rs Ikke fyll helt opp Bensinen trenger plass til ekspandere Passende n...

Page 29: ...ing av denne For mer effektiv batterilading anbefales en 230 V lader som kan kobles til 230 V uttaket p generatoren Batterier med lavere kapasitet enn 60 Ah m ikke kobles til 12 V utgangen er ureguler...

Page 30: ...ilter Kontroller Rengj ring av luftfilter Rengj ring Tennplugg Rengj r eller skift ved behov Ventil Overlat til autorisert servicepersonell kontrollere justere ved behov Rengj ring og skifte av luftfi...

Page 31: ...litt p tennplugghetten samtidig som den trekkes utover Obs Trekk ikke i kabelen men hold i selve tennplugghetten 3 Skru ut pluggen med den medf lgende hylsen 4 Rengj r stiften og kontroller elektrode...

Page 32: ...er at ikke overspenningsvernet er utl st Kontroller at apparatene er fri for feil riktig tilkoblet og at kablene er hele Avfallsh ndtering N r produktet skal kasseres m det skje i henhold til lokale f...

Page 33: ...iedot k ytt ohjeen lopussa Sis llysluettelo Turvallisuus 34 Painikkeet ja toiminnot 35 Asennus 37 Kahva 37 Tukijalat 37 Renkaat 37 K ytt 38 Ennen generaattorin k ynnistyst 38 K ynnist minen 38 Laittei...

Page 34: ...hdon kautta l liit generaattoria rakennuksen s hk j rjestelm n ilman valtuutettua s hk asentajaa Virheelliset liit nn t voivat aiheuttaa s hk verkkoon takavirran joka voi johtaa loukkaantumisiin tai k...

Page 35: ...a Puhdista tarvittaessa Rikastin Sulku vasemmalle Maadoitustangon liit nt Painikkeet ja toiminnot 1 Polttoaines ili n kansi 2 Polttoainemittari 3 Ilmansuodatin 4 Rikastin 5 Sytytystulppa 6 Polttoaineh...

Page 36: ...36 SUOMI 10 1 10 20 10 21 10 19 10 18 10 16 10 15 10 14 10 17 10 11 10 13 10 3 10 6 10 7 10 9 10 8 10 10 10 4 10 5 10 2 10 12...

Page 37: ...ut tukijalkoihin ja asenna sen j lkeen tukijalat rungon etuosan poikkipalkkiin Renkaat Kiinnit renkaat rungon takaosaan ty nt m ll rengasakselit l pi ja kirist m ll lukkomutterilla kiinnikkeen sis puo...

Page 38: ...aske ljy ulos kunnes taso on sopiva 8 Kiinnit ljyn t yt n tulppa paikalleen Polttoaineen lis ys Huom K sittele polttoainetta ainoastaan ulkona l t yt s ili t liian t yteen sill polttoaine tarvitsee ti...

Page 39: ...neraattorin 230 V AC liit nt n l liit generaattoriin akkuja joiden kapasiteetti on pienempi kuin 60 Ah 12 V liit nt on s telem t n eli j nnite vaihtelee moottorin kierrosluvun ja kuormituksen mukaan Y...

Page 40: ...stus Puhdista Sytytystulppa Puhdista tai vaihda tarvittaessa Venttiilin v lys Anna ammattilaisen tai henkil n jolla on riitt v t tiedot ja taidot hoitaa tarkis tus ja s t minen tarvittaessa Ilmansuoda...

Page 41: ...lpan nallihattu Heiluta nallihattua hieman samalla kun ved t siit Huom l ved johdosta Pid kiinni nallihatusta 3 Irrota sytytystulppa pakkauksessa olevalla hylsyll 4 Puhdista tulppa ja tarkista elektro...

Page 42: ...OFF Tarkista ettei ylij nnitesuoja ole lauennut Tarkista ett laitteet ja niiden johdot ovat ehji ja ett laitteet on liitetty oikein Kierr tt minen Kierr t tuote asianmukaisesti kun poistat sen k yt st...

Page 43: ...nahme Kontakt siehe R ckseite Inhaltsverzeichnis Sicherheitshinweise 44 Tasten und Funktionen 45 Montage 47 Griff 47 St tzbeine 47 R der 47 Bedienung 48 Vor dem Start 48 Starten 48 Anschlie en von Ger...

Page 44: ...er Aufbewahrung des Generators immer leeren Vor dem Transport Den Kraftstoffhahn schlie en und die Z ndkerzenkappe von der Z ndkerze l sen Der Generator erzeugt Hochspannung die zum Tode f hren kann D...

Page 45: ...slass links 11 lauslass rechts 12 lstandsmessung leinf ll ffnung rechts Eine inkorrekte Verwendung des Generators kann zu Besch digungen f hren oder seine Lebensdauer verk rzen Den Generator nicht zwe...

Page 46: ...46 DEUTSCH 10 1 10 20 10 21 10 19 10 18 10 16 10 15 10 14 10 17 10 11 10 13 10 3 10 6 10 7 10 9 10 8 10 10 10 4 10 5 10 2 10 12...

Page 47: ...am vorderen Querbalken des Rahmens befestigen R der Die R der an ihren Halterungen am hinteren Teil des Rahmens anbringen Hierzu die Radachsen hindurchstecken und mit der Sicherungsmutter auf der Inne...

Page 48: ...handen eine der lablassschrauben 10 11 ffnen und ausreichend viel l ablassen 8 Den leinf llstutzen wieder festschrauben Kraftstoff nachf llen Hinweis Kraftstoff nur im Freien auff llen Den Tank nicht...

Page 49: ...besteht F r ein effektiveres Laden von Akkus wird ein 230 V AC Ladeger t empfohlen das an den 230 V AC Anschluss des Generators angeschlossen wird Keine Akkus mit einer Kapazit t unter 60 Ah anschlie...

Page 50: ...en oder bei Bedarf wechseln Ventilspiel Von autorisiertem Servicepersonal oder Personen mit ausreichenden Kenntnissen kon trollieren und bei Bedarf justieren lassen Luftfilter reinigen und wechseln 1...

Page 51: ...n an der Z ndkerzenkappe Hinweis Nicht am Kabel sondern an der Z ndkerzenkappe ziehen 3 Die Z ndkerze mit der mitgelieferten H lse herausschrauben 4 Die Z ndkerze reinigen und den Elektrodenabstand pr...

Page 52: ...hutz nicht aktiviert ist Sicherstellen dass die Ger te intakt sowie ordnungsgem an den Generator angeschlossen sind und die Kabel keinen Defekt aufweisen Hinweise zur Entsorgung Bitte das Produkt ents...

Page 53: ...raavien direktiivien ja standardien vaatimukset Erkl rt hiermit dass dieses Produkt die Anforderungen und Bestimmungen folgender Richtlinien erf llt GENERATOR Cotech 40 8890 GG3300B Machinery directiv...

Page 54: ......

Page 55: ......

Page 56: ...oks 485 Sentrum 0105 OSLO SUOMI ASIAKASPALVELU Puh 020 111 2222 S hk posti asiakaspalvelu clasohlson fi INTERNET www clasohlson fi OSOITE Clas Ohlson Oy Maistraatinportti 4 A 00240 Helsinki UNITED KIN...

Reviews: