9. SITING

The modem must be installed in a dry location that respects the relevant ambiental conditions given under 5.TECH-

NICAL DATA.  If sited in a location classified as “Hazardous” it must be installed in a cabinet for electrical equipment 

constructed according to the regulations in force for the class of danger concerned.

The modem can be mounted on a DIN rail and housed in a standard DIN enclosure.

The antenna must be installed in a zone covered by the chosen telephone operator, using, if necessary, the APA 

812 extension.

10. ELECTRICAL CONNECTIONS

Proceed as follows :

• Loosen the four screws (6.

3

) that fix the cover to the base and separate the two parts.

• Mount the base on the DIN rail and check that the securing elements (6.

4

) anchor it securely

• Make the electrical connections according to the diagram and in observance of the safety regulations in force using 

the following cables: : 

– 1.5 mm

2

 for the power supply and the relay control outputs.

– 1 mm

2

 for C-Bus and RS232 for lenght limits see data sheet T 021.

• Switch on power (230 V~) and check its presence at terminals L – N and L1-N1.

• Switch off power, replace cover on base/terminal block and secure it with  the four screws supplied (6.

3

).

• Connect the antenna cable (6.

8

) to the coupling (6.

6

) using the female-female connector (6.

7

You are advised not to insert more than two cables in a single terminal and if necessary to use an external junction 

box .

11. C-BUS LINE CHARACTERISTICS

The C-Bus line’s communication speed can be set at 1200, 2400, 4800 and 9600 baud.

To set the desired speed, the TCB 908 tester can be used, connected to a PC.

The desired speed can be selected via the SWC 701 Remote Management software.

The C-Bus line can be up to 2000 metres long, with 100 slave units at the most, regardless of transmission 

speed.

12. SIM CARDS

12.

1

 Purchase of SIM CARD.

You are advised to purchase the SIM card from your chosen GSM network service provider for business networks.

When purchasing, it is essential to request a card enabled for the transmission and reception of DATA with the 

following communication modes: AUTOBAUDING; ASYNCHRONOUS; NOT TRANSPARENT (correction data 

enabled).

12.

2

 Inserting SIM card in GSM 622

Before inserting the SIM card in the modem 

it is essential 

to disable the PIN code of the card.

To do this, use a GSM cellular telephone and insert the SIM 

card in it; then, following the instructions received from this 

telephone, disable the PIN code. 

To install the SIM card in GSM 622 proceed as follows:

– Ensure that the modem is switched off; 

You must NOT 

insert or remove the SIM card while the modem is 

switched on.

– Using a pointed object, press button (1) to extract card 

holder (2).

– Insert SIM card (3) in the holder making sure that it is the 

right way round

– Push in the card holder until it clicks into place.

– Power the modem.

12.

3

 GSM network signal strength indicator

LED (7.

2

) indicates the status of the modem :

 

- off 

:

 modem not ready;

 

- on 

:

 searching for signal, SIM card not inserted, absence of antenna or in reset stage

 

- slow flashing  

:

  signal present;

 

- rapid flashing 

:

  modem transmitting; 

To know exactly the signal quality you must: 

– connect GSM 622 to a computer (with SIM inserted and powered) and

– using a communication program or SWC 701 telemanagement program, send instruction “

AT + CSQ

” to the mo-

dem; 

– read the reply coming from GSM 622:

– from 0 to 9 =  

the field is almost always too weak

– from 10 to 15 =  the field is ususlly strong enough

– over 15 =  

the field is good

1

2

3

Summary of Contents for GSM 622

Page 1: ...ate the presence of the GSM signal Every six hours resets itself automatically It is possible to reset manually by connecting a push button switch to terminals E D 3 REFERENCE STANDARDS The protocol details are based on the following standards 1999 5 CE of March 9 1999 R TTE as having been designed in conformity with the requirements of following Reference Standards EN 60950 EN 301 489 1 EN 301 48...

Page 2: ...ended RS232 By inverting Tx and Rx it is possible to connect Coster devices DIN format provided with a serial input C BUS Parallel output for connecting to Coster devices fitted with C BUS parallel input 1 2 3 4 5 6 7 1 Power 2 Presence signal 3 Reset modem 4 Connection 5 Data transmission 6 Data reception 7 Socket for TCB 908 tester 1 Protective cover for electronic components 2 Base with transfor...

Page 3: ...be used connected to a PC The desired speed can be selected via the SWC 701 Remote Management software The C Bus line can be up to 2000 metres long with 100 slave units at the most regardless of transmission speed 12 SIM CARDS 12 1 Purchase of SIM CARD You are advised to purchase the SIM card from your chosen GSM network service provider for business networks When purchasing it is essential to req...

Page 4: ...ENSIONS Update diagram Overall dimensions 02 03 09 AM 01 3 11 3 0 GSM network signal strength indicator Aggiornati dati del segnale di campo 04 02 10 AM 02 1 and 3 5 and 11 C Bus transmission speed updated COSTER TECNOLOGIE ELETTRONICHE S p A Sede Legale 20132 Milano Via San G B De La Salle 4 a E mail info coster info Web www coster eu COSTER CONTROLLI TEMPERATURA ENERGIA Head Office Sales Via San ...

Reviews: