17. OUTSIDE COMPENSATION  OF TEMPERATURE

Compensation functions are only enabled if the outside detector B2 is connected. Such functions
can be as follows:

• Compensation of desired flow Heating and Cooling temperatures;

• Summer compensation of desired room or flow Cooling temperatures;

Desired temperature adjustment values,
Resulting from compensation, are displayed in

and

17.

1

 Climatic compensation of desired flow Heating and Cooling temperatures

This function can be only used if detectors B1 and B2 are connected, and Detector B3 is not
connected. It is useful when the primary air system, in addition to ensuring air circulation, is also
intended to make up for ambient dispersion.

Desired flow Heating temperature

The controller increases desired temp. when outside temperature drops,
according to settings:

• Heating Comp. : NO = function disabled

YES = function enabled

• Opt

: xx

 c = default outside temp. : winter

• Fpt

: xx

 c = default flow temp. : winter

Desired flow Cooling temperature

The controller decreases desired temp. when outside temperature
increases, according to settings:

• Heating Comp. : NO = function disabled

YES = function enabled

• Opt : xx

 c = default outside temp. : summer

• Fpt

: xx

 c = default flow temp. : summer

17.

2

 Summer compensation of desired room Cooling temperature

This function can be only used if detectors B2 and B3 or B1, B2 and B3 are connected. It is useful to
prevent excessive temp. differences between room and outside.

The controller maintains temp. at a constant level

until outside temp. exceeds the value 

T

°

Coo

 + 

t

°

, when this occurs 

T

°

Coo

is increased by 1

°

C per each 

°

C increase in outside temp.

• Heating Comp.:

NO = function disabled

YES = function enabled

• Diff. O. T-R .T :

xx

 c = maximum allowed difference between

outside and room temp.

Co o l

T . Room

De s i r . : 2 5 . 0 c

±

0 . 0

M0.

7

Summer Compe n : NO
D i f f . O . T - R . T :

6 c

M2.

10

He a t i n g Comp . : NO
Pp t : – 1 0 c F p t : 5 0 c

M2.

8

Co o l i n g Comp . : NO
Op t : + 3 5 c F p t : 1 0 c

M2.

9

De t e c t o r s L a y o u t

1 2 – – – – – –

M3.

1

De t e c t o r s L a y o u t

1 2 3 – – – – –

M3.

1

F l ow Coo l

T .

De s i r . : 2 5 . 0 c

±

0 . 0

M0.

7

F l ow He a t .

T .

De s i r . : 2 0 . 0 c

±

0 . 0

M0.

5

F l ow He a t .

T .

Compe n s a t . :

±

0 0 . 0

M0.

6

F l ow Coo l

T .

Compe n s a t . :

±

0 0 . 0

M0.

8

+

+

T

°

f

Hea

t

°

o

T

°

f

Hea

T

°

f

Hea

f

p

T

°

o

p

T

°

+

+

T

°

f

Coo

t

°

o

T

°

f

Coo

T

°

f

RCoo

f

p

T

°

T

°

o

p

+

+

T

°

Coo

t

°

o

T

°

Coo

T

°

Coo

t

°

1

°

C

1

°

C

Summary of Contents for DTU 614 C2 Eng.

Page 1: ...ve output configurable for air mixing control based on temperature comparison with minimum external air limit external air control for room dehumidification with compensation of dew temperature on glass windows and with minimum external air limit heat recuperator On Off control according to room external temperature comparison vapor operated humidifier setting by means of a 0 10 V control One 3 wi...

Page 2: ...ion cover 2 Support base with transformer relays and terminal boards 3 Screws for securing cover to base 4 DIN rail securing elements 5 DIN rail release lever Temp proportional band base value Heating room B3 o B1 B3 1 2 40 C Heating flow B1 1 10 40 C Various temp proportional band multipliers Heating flow B1 B3 Pb amb x 0 5 5 20 Cooling temperatures Pb heat x 0 5 20 preheating B4 Pb heat disch x ...

Page 3: ...e c1 as only On Off control set OFF in the Program setting M0 2 and M0 4 Possible Season Switching M3 2 modes No ss Winter Summer Based on Outside Temp Based on Seasons Ss Win On Off according to Winter Program setting M0 2 Ss Sum On Off according to Summer Program setting M0 4 Season switching M3 2 must be through ss control Ss Win and c1 open On Off according to Winter Program setting M0 2 Ss Wi...

Page 4: ... an inside wall away from windows doors and sources of heat no alcoves scaffolds or hangings STA 010 extract air It should be installed upstream with respect to the extract fan 9 5 Duct mounting humidity detector B6 Extract air It must be installed upstream with respect to the extract fan Discharge air It should be installed downstream with respect to the discharge fan 9 6 Preheating temperature d...

Page 5: ... e ss Gr oup M3 7 Send i ngA l a rms NO PassWTe l eman NO 10 COMMUNICATION 10 1 C Bus Telemanagement Communication for more detailed information please see Technical Sheet T 021 Through the C Bus output DTU 614 can be managed remotely two way data communication by means of one or more local PC s and or a remote central computer via telephone network From the PC s it is possible to view and or chan...

Page 6: ...ptional 11 2 Room temperature and humidity control with flow temperature limits De t e c t o r s La you t 1 2 3 5 6 8 M3 1 B1 Flow temp detector B2 Outside temp detector for compensation only B6 Room or extract humidity detector Rt Temperature set point adjuster optional RH Humidity set point adjuster optional 11 3 Flow temperature and room or flow humidity control De t e c t o r s La you t 1 2 5 ...

Page 7: ...er optional Y Heating modulating control Ys Progressive air damper control dehumidification Us e De t ec t o r B4 DEWPOINT M3 3 De t e c t o r s La you t 2 3 M3 1 Ys Con t r o l DAMP TEM M3 6 B3 B2 Ys DTU 614 T T Rs Rs 1 3 2 B2 0 24 V 24 M B5 B4 M B3 B2 M B1 DTU 614 B6 24 0 0 B3 B7 G 24 D E2 B8 E1 C Ys 0C Ys T T 24 1 Y1 3 0 2 B3 B2 DTU 614 T T M Ys U1 B2 0 24 V 24 M B5 B4 M B3 B2 M B1 DTU 614 B6 2...

Page 8: ...nsation B3 Room or extract temp detector B6 Room or extract humidity detector Mu Humidifier On Off control Mv Fan On Off control Rt Temperature set point adjuster optional RH Humidity set point adjuster optional Y On Off heating control De t e c t o r s Layou t 1 2 3 5 6 7 8 M3 1 Y MODULAT i NG Run T ime x xs M3 4 Y HEAT I NG M3 5 Se ason Sw i t ch i ng NO M3 2 De t e c t o r s Layou t 1 2 3 5 6 7...

Page 9: ... Heat pump season control 13 5 1 Winter heating summer cooling On Off battery with heat pump season switching 1 Humidifying On Off unit B1 Flow temp detector B2 Outside temp detector for compensation B3 Room or extract temp detector B6 Room or extract humidity detector Mu Humidifier On Off control Mv Fan On Off control Rt Temperature set point adjuster optional RH Humidity set point adjuster optio...

Page 10: ...p detector B4 Preheating temperature detector B6 Room or extract humidity detector B7 Frostprotection detector Mu Adiabatic humidifier On Off control Mv Fans Y Winter preheating control Y1iwin Winter postheating control Y2 Summer cooling dehumidifying control Y3sum Summer postheating control Rt Temperature set point adjuster optional RH Dehumidification set point adjuster optional for humidifying ...

Page 11: ...b Cooling room Pb heating room x 0 5 1 C Pb Cooling flow Pb heating flow x 0 5 5 C Pb Preheating Pb flow heating x 1 0 10 C Pb Dew point Pb room heating x 1 0 2 C 15 OPERATION DTU 614 is a microprocessor operated digital controller for temperature and relative humidity control in air handling units composed of 1 unit with 3 wire modulating control or 1 2 or 3 stage On Off control The unit can have...

Page 12: ...BpHea proportional band s range The minimum value T fminHea helps eliminate annoying cold drafts in the room Min c Max c Cooling flow temp min and max values determine the BpCoo proportional band s range The controller compares desired flow temperatures for Heating T minHea and for Cooling T fCoo and for Cooling T fCoo against the temperature measured by the discharge air detector B1 and derives t...

Page 13: ... use requires unit to be off With with contact ss in summer D E2 closed mode is When Summer Program in use requires unit to be operating When Summer Program in use requires unit to be off With with contact ss in winter D E1 closed mode is When Winter Program in use requires unit to be operating When Winter Program in use requires unit to be off and contact c1 D E1 is closed When Winter Program in ...

Page 14: ...erature The controller decreases desired temp when outside temperature increases according to settings Heating Comp NO function disabled YES function enabled Opt xx c default outside temp summer Fpt xx c default flow temp summer 17 2 Summer compensation of desired room Cooling temperature This function can be only used if detectors B2 and B3 or B1 B2 and B3 are connected It is useful to prevent ex...

Page 15: ... limit dew buildup on swimming pool windows detector B4 should be placed so that it adheres to the glass 19 1 Preheating temperature control If detector B3 or detectors B1 and B3 are connected the controller calculates preheating temp T pre according to the following Condensation curve calculated on the basis of room temp t r and room humidity h a actual values Minimum value set in M0 12 Manual ad...

Page 16: ...If the controller has turned on the Mv fan when the Qaf load value reaches the 100 value the controller turns the fan off and cancels the Ys air damper control signal closing when it drops to 0 the controller turns on the fan and restores the air damper control signal Des F r os t p 7 0c Ac t F r os t p 35 0c M0 14 21 HEAT PUMP CONTROL If the Air Handling Unit is composed of a direct exchange heat...

Page 17: ...Frostprotection Qfrp antifreeze control through one valve controlled by another controller OFF Not used in current season 22 2 Mu adiabatic humidifier control output Output Mu 8 9 10 uses the Qhumi load to control the adiabatic humidifier While operating when setting is ON only if the fan control Mv is on and only in Winter if season switching is activated Off when setting is OFF in Summer if seas...

Page 18: ...m temperature T r and higher than the target T rCoo value A signal converter is required to transform the 0 10V signal into an On Off control 23 5 Minimum flow temperature limit In the cases shown When actual flow temperature t f drops below the minimum flow value T fmin the controller shuts outside air with a modulating action 23 6 Minimum outside air In the cases shown The minimum amount of outs...

Page 19: ...essive season periods Result no intermediate periods From Oct 15 to Apr 15 Y setting and Ycs season switch on Winter From Apr 16 to Oct 14 Y setting and Ycs season switch on Summer Shortened season periods Result intermediate periods with unit off From Oct 15 to Apr 15 Y setting and Ycs season switch on Winter From Apr16 to May 14 Y setting on OFF and Ycs season switch on Winter From May15 to Sept...

Page 20: ...normal program Set the number of year periods to be used in order to eliminate unused display pages For each year period select the program to be used 7 DAY 1 4 24 HOUR 1 25 ON OFF Set data for each individual period Per 01 selection of available periods Start NO year period not used 00 year period used start time midnight 12 year period used start time 12 o clock noon From t o start and end day a...

Page 21: ...ted and Dew point desired and actual temperature only if B4 is connected and Setting of desired battery frostprotection temperature and actual value only if B7 is connected Output Y load value Preheat or Heat or Ht P Hea or Cool or Frostprotection Output Ys load value DampTemp or Recuper or Dehumid or Humid Output Mu load value Humidification Battery frostprotection function load value 26 4 Data r...

Page 22: ...are disabled except clock alarm 8 Use the and keys to enable desired alarms entering numbers in place of the dashes Number flashing the alarm is on Alarm limit values and delays can only be changed via computer Types and reasons of alarms 1 flow temperature difference if only B1 is connected for actual temp lower than T fHea when Y Heating or higher than T fCoo when Y Cooling 3 room temperature di...

Page 23: ...M i n im Ou t s i de T He a t Pump 0c Se ason Sw i t ch i ng NO Use de t e c t o r B4 PREHEAT I NG Ys Rap i dFunc t i on S t a r t NO Ou tWi n t e r T 20c De l a y 2 4o r e Ou t Summer T 2 5c De l ay 4h r s Cu r r en t mode ON Wi n t e r Des P r he a t 1 5 0c Ac t P r he a t 1 5 0c Ca l cu l a t ed F l ow Coo l i ng T 2 0 0c Ac t ua l f l ow Tempe r a t 3 5 0c 12 18 MONDAY 10 03 0 0 GMT TECHN I CA...

Page 24: ... M0 17 Actual flow temp as measured by B1 26 3 Displayed if B1 and B3 are connected Ca l cu l a t ed F l ow Coo l i ng T 20 0c M0 16 Cal Controller calculated Flow temperature for cooling 26 3 Displayed if B1 and B3 are connected Hea t T Room Des i r 20 0c 0 0 M0 5 Required heating temperature and adjustment through set point adjuster Ht only if configured 16 1 Displayed if B3 or B1 and B3 are con...

Page 25: ...e used 0 5 Wi n t e r Season F r 15 10 t o 15 04 M1 19 Winter season start and end dates 25 5 How many annua l pe r i ods 0 M1 16 Selection of amount of year period programs to be used 0 25 Eliminates unused display pages 25 4 P r og r Pe r i od 1 OFF M1 17 Program selection for the entire year period 1 7 DAY 1 5 24 HOUR 1 25 ON OFF Other 6 page groups according to data in M1 16 Displayed only if ...

Page 26: ...me in minutes 16 2 Displayed if B3 or B1 and B3 are connected Displayed if only B1 is connected M2 2 Tempe r F l ow I n t eg r T ime 10m Tempe r Room P r op Band 2 0c M2 1 Heating proportional band in C If B3 or B1 and B3 are configured 16 2 Based on this value the controller derives other functions proportional bands using the multipliers set in the SETTING menu Tempe r F l ow P r op Band 10 0c I...

Page 27: ...yed if M3 2 setting is different from NO Output Ys action Ys Con t r o l DAMP TEM M3 6 Select Ys action DAMP TEM HUMIDIF DEHUMID RECUPER 23 A l a rms Func t i ons 8 M3 9 Function alarms enabled Default config Only alarm 8 enabled cannot be disabled 27 1 1 discharge air alarm B1 3 room temp or extract air alarm B3 4 preheating or dew point temperature alarm B4 6 humidity difference B6 7 battery fro...

Page 28: ...S ON 1 ON 1 2 OFF With Y 3 STAGES ON 1 ON 2 ON 1 2 OFF With Ycs WINTER SUMMER With Mu Mv 0N OFF With Ys 0 VOLT 5 VOLT 10 VOLT COSTER CONTROLLI TEMPERATURA ENERGIA COSTER UNI EN ISO 9002 CISQ CSQ cert n 9115 COEE Head Office Sales Tel 39 02 2722121 TI Tel 39 02 45476193 FW Fax 39 02 2593645 Reg Off Central Southern Tel 39 06 5573330 Fax 39 06 5566517 Orders and Shipping Tel 39 0364 7732 00 02 Fax 3...

Reviews: