Make sure that all the wires are properly connected, mount top
cover and power up the wiring centre - the
green
„Power” indicator
LED will illuminate.
These are used to set in minutes the delay time (overrun time).
Default setting is „0”.
0-5 values specify the time in minutes. E.g. when jumper is set to
value „0”, the module will turn off as soon as the thermostats stop
calling for heat. If jumper will be set to the value „5”, the module will
turn off 5 min after the thermostats stop calling for heat.
They are used to select the zone which turns on the module. Default
setting is „P”.
P
– all zones start the module
1, 2, 3, 4, 5, 6
– select the specific zone which turns on the module.
Remove the top cover of the wiring centre.
Note:
Before connecting the module, disconnect the main power
from the
CKL6230N
wiring centre.
Connect the module to the serial connector.
J U M P E R S D E S C R I P T I O N
L E D I N D I C AT I O N
I N S TA L L AT I O N
W I R I N G D I A G R A M
JUMPERS P, 1, 2, 3, 4, 5, 6
PUMP CONTROL
JUMPERS 0-5
1
2
3
L E D
D E S C R I P T I O N
Green
Pump is running
Red
Pump is off
L
N
min
Nachlaufzeit
P
1
4
0 5
5 6
2 3
L
N
min
Nachlaufzeit
P
1
4
0 5
5 6
2 3
L
N
min
Nachlaufzeit
P
1
4
0 5
5 6
2 3
max 5 (2) A