Cosel PBA1000F Instruction Manual Download Page 7

*

Synchronous rectification method is employed for these products 

and therefore you cannot use them in parallel operation without 
OR diode.

¡

Even a slight difference in output voltage can affect the balance 
between the values of I

1

 and I

2

.

Please fine-tune the output voltage so that a current from each 
power supply does not exceed its rated current and a balance 
among output current values is kept.

l

1

, l

2

 

[

 rated current value

¿ 

PBA300F, PAB600F, PBA1000F and PBA1500F

¡

You can use the power supplies in parallel operation by connect-
ing units as shown in Fig.4.3.
Please parallelly connect ±S, VB and CB of each power supply in 
parallel operation and connect ±S and ±M on CN1 of the master 
power supply.
When the power supplies are shipped from a factory, they come 
with a dedicated harness (H-SN-19) being mounted on CN1.
Please remove the dedicated harness (H-SN-19), which is mount-
ed on CN1 of the slave power supply, and use an optional har-
ness, H-PA-3, to connect ±S, VB and CB parallelly.  
Differences in the output current values among the power supplies 
in parallel connection are 10% at most.  Please make sure that 
the sum of the output current values does not exceed a value ob-
tained from the right side of the following equation.

       (Output current in parallel operation)
                 = (Rated current per unit) 

X

 (Number of units) 

X

0.9

¡

When the number of units in parallel operation increases, the in-
put current also increases.  Please design input circuitry (including 
circuit pattern, wiring and current capacity for equipment) carefully.

¡

Please make sure that the wiring impedance of a load from each 
power supply becomes even.  Otherwise, the output current bal-
ance circuit may become inoperative.

¡

The maximum number of units you can use in parallel operation is 
5.

4.2 Parallel Operation/Master-slave Operation

¿ 

PBA10F,  PBA15F,  PBW15F,  PBA30F, 

PBW30F,  PBA50F,  PBW50F,  PBA75F, 

PBA100F and PBA150F

¡

You can use the power supplies in parallel operation by connect-
ing units as shown below.

¡

You can adjust the output voltage in parallel operation by adjusting 
a potentiometer of just one power supply. 
To do so, select one power supply as the master unit and turn the 
potentiometers of the other (slave) power supplies clockwise to 
the end.
Once you have done this, you can adjust the output voltage by 
turning the potentiometer of the master unit.

¡

If you use the remote sensing function in parallel operation, con-
nect paraS and -S of slave power supplies must be con-
nected to master and connect the sensing wire from the master 
unit to the load.

¡

You cannot parallelly operate power supplies with different output 
voltage or electrical power.

¡

If an output stops (through the remote ON/OFF circuit or due to 
an input shutoff or failure) in parallel operation, the LED of the 
stopped unit lights off.

¡

When the load becomes 10% or less of the rated current, the PG 
signals may turn ”High” and the fan may stop.  In this case, the 
LED also lights off.

4.3 N+1 Parallel Redundancy Operation

¿ 

PBA300F, PAB600F, PBA1000F and PBA1500F

¡

You can have N+1 redundancy operation for improved system reli-

ability. 

¡

If you add one extra power supply in parallel operation, even if 

one of the power supplies in your system fails, the remaining non-
failed power supplies continue to sustain the system.  If one of the 
power supplies stops operating, the output voltage may change 
about 5%.

¡

If you have any questions about series, parallel and N+1 redun-
dancy operations, please contact us.

Unit type

Instruction Manual

A-38

PB

Unit type

Instruction Manual

A-39

PB

Fig.4.3 Example of parallel connection

(PBA1500F)

Fig.4.2 Example of connecting in parallel operation

��

��

�����
������

�����
������

� ��

�� ���

��

��

��

� ��

��

���

���

���

� ��

�� ���

��

��

��

� ��

��

���

���

���

� ��

�� ���

��

��

��

� ��

��

���

���

���

������� �������

������� ������

������� ������

������ �������

������������

�����������

�����������

����

Summary of Contents for PBA1000F

Page 1: ...bling and Installation A 40 A 35 A 35 A 35 A 35 A 36 A 36 A 36 A 37 A 38 4 1 Series Operation 4 2 Parallel Operation Master slave Operation 4 3 N 1 Parallel Redundancy Operation 5 1 Installation 5 2 D...

Page 2: ...output 12V 0 1A RC1 Remote ON OFF AUXG Auxiliary output GND N C No connection PG Alarm PGG Alarm GND Matching connecters and terminals on CN1 CN2 and CN3 Connector Housing Terminal Mfr CN1 CN2 CN3 S1...

Page 3: ...rcuit When you turn the power ON OFF repeatedly within a short period of time please have enough intervals so that the inrush current limiting circuit becomes operative When the switch of the input is...

Page 4: ...1 gives you only an estimate Please contact us if you need accurate numbers Output voltage Xrated output voltage 1 Please do not apply an external voltage of 0 7V or less or 3 0V or more There is more...

Page 5: ...ltage may dramatically fluctuate because of an imped ance of wiring and load conditions Please check and evaluate carefully before using the remote sensing function If the output voltage becomes unsta...

Page 6: ...High vary depending on models and conditions PBA300F and PBA600F less than 1 second PBA1000F and PBA1500F less than 10 second 2If the output voltage is turned off through a remote ON OFF cir cuit the...

Page 7: ...imum number of units you can use in parallel operation is 5 4 2 Parallel Operation Master slave Operation PBA10F PBA15F PBW15F PBA30F PBW30F PBA50F PBW50F PBA75F PBA100F and PBA150F You can use the po...

Page 8: ...PBW30F Input Voltage Derating Curve Input voltage derating curve is shown in Fig 5 2 PBA300F PAB600F PBA1000F and PBA1500F Ambient Temperature Derating Curve Derating curve depending on an ambient te...

Page 9: ...ting curve Unit type Instruction Manual A 41 PB Fig 5 3 Ambient temperature derating curve Ambient temperature C Load factor 80 70 80 90 100 30 40 50 60 70 71C 0 10 20 30 40 50 60 20 10 20 0 10 Fig 5...

Page 10: ...filter Examples of Constant Values of the External Noise Filter L1 0 45mH L2 0 45mH C1 0 1 F C2 0 1 F C3 0 1 F C4 4700pF C5 4700pF R1 2MW R2 2MW 6 Others 6 1 Output Current Monitor PBA300F PBA600F PB...

Page 11: ...ns Doing so may cause a failure F1 PBA600F PBA1000F PBA1500F Option F1 units have a longer life fan instead of a standard fan This option is not available for PBA300F Differences from standard version...

Page 12: ...PBW30F PBA50F and PBW50F 2 Matching Molex Connectors and Terminals for PBA75F PBA100F and PBA150F R PBA50F PBW50F PBA75F PBA100F and PBA150F You can control output ON OFF remotely in Option R units To...

Page 13: ...5F and PBA30F has been filed Safety agency approvals will be void if the cover is attached after the unit is ex factoried N1 PBA10F PBA15F PBW15F PBA30F PBW30F PBA50F PBW50F PBA75F PBA100F and PBA150F...

Reviews: