background image

STANDARD RECOMMENDED PROCEDURE 006-383 | ISSUE 1 | AUGUST 2008 | PAGE 4 OF 10

=

Step 3:

After removing the required length of outer jacketing of the tight-buffered pigtail, carefully 
cut the aramid yarn off with scissors at the end of the jacketing.

Step 4:

If using jacketed cables, 

remove a minimum of 175 mm (6.9 inch) of jacket on each side 

of the splice to make room for splicing (Figure 3).

Step 5:

If using boots, slide the 900 micron 
boot onto the fiber until it is out of the 
way (Figure 4).

NOTE:

Use the 900 micron boot for 900 micron 
tight-buffered, 900 micron furcated and 
250 micron direct termination 
applications.

Step 6:

For termination on bare 250 micron 
fiber, also slide on the furcation tube 
provided with the CamSplice until the 
tube is out of the way.

Step 7:

Using the Strip Length Gauge and permanent marker, measure and place a visual mark 
at the dimensional markings shown in Figure 3.

Step 8:

To expose bare glass, remove the 44 mm section of 
buffer and coating in two steps using the Dual-Hole 
Stripping Tool (Figure 5).

•  For the 900 micron buffer, use the large V-notch.

•  For the 250 micron coating, use the small V-notch.

Step 9:

Clean the bare fiber with two passes of a Fiber Wipe dampened with Fiber Optic Cleaning 
Fluid.  Do not touch the bare fiber after cleaning it. Do not remove the visual mark.

Step 10:

Proceed to Section 5, Cleaving Fiber.

CAUTION: 

Fiber Optic Cleaning Fluid can cause irritation to eyes on contact. In case of eye 

contact, immediately flush eyes with water for at least 15 minutes. Inhaling fumes may be 
harmful. Use with adequate ventilation. In case of ingestion, consult a physician.

44 mm (1.7 in.)

175 mm (6.9 in.)

13 mm

(0.5 in.)

KPA-2094

900 / 250 micron Tight Buffered Fiber

Jacket

4 mm (0.16 in.)

250 micron coating

44 mm (1.7 in.) bare fiber

900 micron Furcated Fiber

900 micron

tubing

9 mm

(0.35 in.)

Figure 3 — Remove Jacket, if using Jacketed Cable

KPA-2100

900 micron Fiber

250 micron Fiber using Furcation Tube

Figure 4 — Slide Boot out of the Way

900 Micron

250 Micron

KPA-0966

Figure 5 — Expose Bare Fiber

Summary of Contents for CamSplice FBC-017

Page 1: ...ode optical fibers see Table 1 on page 2 This document describes and illustrates splicing both loose tube and tight buffered fibers with the CamSplice Mechanical Splicer The CamSplice mechanical splic...

Page 2: ...ck Permanent Marker 2104499 01 4 Fiber Optic Cleaning Fluid 2104494 01 5 Fiber Wipes 2104493 01 6 FBC 017 Cleaver FBC 017 7 CamSplice Installation Tool 2104041 01 8 Cable Jacket Stripping Tool TL OSE...

Page 3: ...osure to laser light be suspected arrange for an eye examination immediately NOTE Fiber optic cable is sensitive to excessive pulling bending and crushing forces Consult the cable specification sheet...

Page 4: ...bare glass remove the 44 mm section of buffer and coating in two steps using the Dual Hole Stripping Tool Figure 5 For the 900 micron buffer use the large V notch For the 250 micron coating use the sm...

Page 5: ...lamps are clean and free of fiber Refer to Section 8 Maintaining Cleaver for instructions on cleaning the clamps if necessary Step 2 Squeeze buttons A and B Figure 6 at the same time to open the clamp...

Page 6: ...fiber squeeze Button B and remove the cleaved fiber Figure 9 NOTE Once the fiber is cleaved do not clean the fiber or allow it to contact anything If the cleaved fiber does contact something repeat fi...

Page 7: ...he first fiber against the second until there are equal bends in the fibers with approximately 10 13 mm 3 8 to 1 2 inch deflection Step 5 Slowly rotate both levers down to actuate the CamSplice Figure...

Page 8: ...rcation tubing into the lead in tube on each side of the splice until the tubing stops Step 2 Capture lead in tube inside the notched area of the crimp tool Crimp lead in tube on each side of the spli...

Page 9: ...Clamp A gently pull the wipe out Step 5 Dispose of the used wipe Do not use wipe more than once 8 2 Clean the Blade Step 1 Dampen the tip of one of the 1 25 mm cleaning sticks with Fiber Optic Cleanin...

Page 10: ...tton B as shown using a 1 16 inch Allen wrench Figure 20 NOTE Rotate the cleaver s orientation to prevent the blade from falling out of the cleaver Step 2 Remove the Blade Capture Block using a 1 16 i...

Reviews: