Locate the cooler within 2 metre’s of an earthed, switched, 13 Amp, 230V 50Hz socket
which is accessible for isolation of the equipment. The socket must be installed to comply
with current IEE regulations.
Site the cooler on a firm level surface, protect from physical damage and do not place
items on top of, or underneath the cooler.
Clear space must be provided above the unit. Allow 50mm clearance around the unit to
aid air circulation and keep the front of the unit clear to allow an unimpeded air supply to
enter the cooler.
Air vents should never become obstructed or blocked.
Access should be possible to the front panel for ease of service.
Do not stand on this unit.
Installation
General
WARNING - The appliance must be earthed.
If not already fitted, fit the appropriate electrical plug to the service cord. The fuse rating
is stated on the rating plate.
With the unit unpacked and in position, remove all coil caps, but do not connect to an
electrical supply at this stage.
Filling the product water bath.
Do not use de-ionised water or add any substance to the water (unless approved by
Cornelius).
Do not leave hose pipes unattended whilst filling the product water bath as the unit may
become flooded.
Open the filler / inspection hatch on the lid of the cooler.
Fill with cool clean water until liquid starts to flow from the overflow
Stop filling and close the filler / inspection hatch on the lid of the cooler
The overflow is a 15mm connection. A fitting or pipe can be pushed directly into this to
direct the condensate water to drain
Discharge unit (water cooled models)
The discharge cooler should be mounted on an exterior wall, not south facing, and provide
access for pipes and electrical cable to the base unit (maximum 50m). If no exterior wall is
available then mount inside on a wall in a cool room with plenty of fresh air ventilation. Avoid
warm areas (i.e. cupboards or small storerooms). Secure the discharge cooler to the chosen
location and fix (follow instruction guidance from the discharge cooler).
Using a minimum 1.5mm
2
two core cable, connect the Discharge Cooler to the remote W/C
cooler. Connect the two core cable to the quick fit terminal block, this is located at the rear of the
W/C cooler (Note: This is a nominal 24V 50Hz supply).
Complete the glycol circuit by connecting the pipe work between the remote W/C cooler and the
discharge cooler utilizing 15mm Service Valves.
WARNING - As the glycol lines will circulate a warm glycol mix it is important for safety reasons
that suitable tubing is used. Consult a specialist tubing manufacturer or contact Cornelius.
WARNING - PVC tubing, whether braided or not, is not suitable for this application.
Summary of Contents for 06 1 3601 Series
Page 13: ...5 Product Photos Index21 AC Heat Dump Exchange Unit Index21 WC...
Page 19: ...Exploded View Index21 AC Model 06 1 3601XX 1 2 4 6 7 8 11 3 5 10 12 14 15 16 17 9 13...
Page 21: ...Exploded View Idex21 WC Model 06 1 3602XX 3 20 1 15 17 12 4 10 6 8 9 11 13 19 2 7 14 5 16 18...
Page 22: ...8 Wiring Diagram Index21 AC Model 06 1 3601XX...
Page 23: ...Index21 WC...
Page 24: ......