2.2 Installation Instructions
Please read carefully before installing the unit
Please follow these instructions carefully. Only if the remote unit is properly installed and
maintained will trouble free operation and customer satisfaction be achieved.
General description
This is a remotely sited cooler used for cooling drinks such as beer, lager, cider & stout.
Incorporating mechanical temperature control this unit is suitable for the utilization of water as
the product cooling medium and for the formation of an ice reserve.
A recirculation pump provides both constant agitation of the water bath and a flow of re-
circulating chilled cooling medium for python cooling. The remote cooler is fully automatic,
therefore, the electrical supply must not be interrupted (unless access for maintenance is
required), otherwise reduced performance and reliability will occur.
Safety
Read this booklet before undertaking installation or maintenance.
Recognize safety alerts – isolate the power supply before removing panels.
DANGER -
Indicates an immediate hazardous situation which, if not avoided, WILL result in
serious injury, death, or equipment damage.
WARNING - Indicates an immediate hazardous situation which, if not avoided, COULD result
in serious injury, death, or equipment damage.
CAUTION - Indicates an immediate hazardous situation which, if not avoided, MAY result in
minor or moderate injury, or equipment damage.
Handling & transportation
Keep the remote cooler in an upright position and do not drag over rough floors or down
steps.
Upon receipt, unpack the unit carefully and visually inspect for any damage which may
have been sustained during transit. Record the nature of any damage on the courier’s
delivery note and, at the same time inform your supplier.
Once the unit is in position, do not move when filled with water
Installation
Installation must only be carried out by suitably trained person and must comply with
national and local codes for connection to electrical supplies.
It is recommended that the installation is protected by an RCCB (Residual Current Circuit
Breaker).
Siting
Remote A/C & W/C Units
Remote units are designed for indoor use only.
The remote units may be sited within cooled cellars, store rooms or other appropriate
internal areas where the ambient air temperature is between 5°C and 43°C (A/C), 38°C
(W/C).
Remote coolers should not be exposed to liquid spillage, spray, steam or humidity at a
higher level than 90% rh.
Site the cooler within 40 metre’s of the point of dispense.
Summary of Contents for 06 1 3601 Series
Page 13: ...5 Product Photos Index21 AC Heat Dump Exchange Unit Index21 WC...
Page 19: ...Exploded View Index21 AC Model 06 1 3601XX 1 2 4 6 7 8 11 3 5 10 12 14 15 16 17 9 13...
Page 21: ...Exploded View Idex21 WC Model 06 1 3602XX 3 20 1 15 17 12 4 10 6 8 9 11 13 19 2 7 14 5 16 18...
Page 22: ...8 Wiring Diagram Index21 AC Model 06 1 3601XX...
Page 23: ...Index21 WC...
Page 24: ......