Corken ZV200 Installation, Operation & Maintenance Manual Download Page 6

7.  After the setting of the internal relief valve is confirmed, 

open the shut-off valves located on the pump discharge 
line and the bypass return line and resume normal 
operation of the pump.

8.  To confirm the setting for the ZV200 external bypass 

valve, slowly close the shut-off valve in the pump’s 
discharge line and record the pressure shown on the 
gauge. The difference between the pump’s discharge 
pressure and the tank pressure (before pumping) is 
the setting of the external bypass valve.

8.  If the pump is equipped with an internal relief valve, 

the ZV200 external bypass valve should be set 20–25 
psi (1.38 to 1.72 bar) below the setting of the pump’s 
internal relief valve. Following this guideline ensures 
the liquid does not recirculate through the internal 
relief valve and eliminates the possibility of erratic 
“hunting” between the two valves.

9.  Reopen the shut-off valve in the pump’s discharge line 

and resume normal operation of the pump. Record the 
pressure shown on the gauge. The difference between 
the pump’s discharge pressure and the tank pressure 
(before pumping) is the normal operating pressure of 
the system.

10. If possible the setting of the ZV200 external bypass 

valve should be 15 psi (1.03 bar) higher than the normal 
operating pressure of the piping system. An operating 
pressure near the external bypass valve setting may 
cause the liquid to recirculate unnecessarily.

11. Adjust the pressure setting of the ZV200 external 

bypass valve if necessary. The external bypass valve 
can be adjusted by removing the valve cap and 
loosening the locknut. 

  WARNING: Use caution when removing the valve 

cap and follow the procedures below .

a. To 

increase the pressure setting, loosen the 

locknut and turn the adjusting screw 

clockwise.

b. To 

decrease the pressure setting, loosen the locknut 

and turn the adjusting screw 

counterclockwise.

12. 

Once a satisfactory pressure adjustment has 
been achieved, attach the “tamper-proof” seal 
furnished with the external bypass valve to prevent 
unauthorized adjustments.

Notice!

1.  If the external automatic bypass valve is sized and set 

correctly, a manual or hand operated bypass valve–
if applicable–should remain in the closed position 
during normal operation. Keeping the manual or hand 
operated bypass valve closed ensures the external 
automatic bypass valve operates in a normal capacity.

2. Annual inspection and testing of the internal relief 

valve–if applicable–and the external automatic bypass 
valve are recommended. For testing procedures refer 
to the adjustment procedures listed in this manual.

Stationary applications equipped with an electric 

motor drive:

1.  Install liquid-filled pressure gauges equipped with a 

needle valve or snubber in the following locations:

a. Pump discharge gauge port or inlet side of the 

bypass valve.

b.  Supply tank and/or pump suction.

2.  Attach an ammeter to a motor lead of the electric motor.

3.  Remove the valve cap on the ZV200 external bypass 

valve and adjust to the lowest pressure setting by 
turning the adjusting screw 

counterclockwise until 

spring tension is no longer present. 

Note: Do not 

remove the adjusting screw .

4.  Make sure the shut-off valves on the pump discharge 

line and bypass return line are in a fully open position.

5. Start the pump and circulate the liquid back to the 

supply tank using the discharge line.

6. Slowly close the shut-off valve located on pump 

discharge line so all of the liquid flows through the 
external bypass valve.

7. Slowly 

increase the setting of the ZV200 external bypass 

valve by turning the adjustment screw 

clockwise until 

the ammeter indicates the full-load current indicated on 
the motor nameplate or required differential pressure is 
reached. Record the pressure on the gauge mounted 
on the inlet side of the bypass valve.

9.  If the pump has an internal relief valve, the ZV200 

external bypass valve should be set at least 20–25 psi 
(1.38 to 1.72 bar) below the setting of the pump’s built 
in relief valve. Following this guideline ensures the 
liquid does not recirculate through the internal relief 
valve and eliminates the possibility of erratic “hunting” 
between the two valves.

10. If possible the setting of the ZV200 external bypass 

valve should be 15 psi (1.03 bar) higher than the normal 
operating pressure of the piping system. An operating 
pressure near the external bypass valve setting may 
cause the liquid to recirculate unnecessarily.

11. Adjust the pressure setting of the ZV200 external 

bypass valve if necessary. The external bypass valve 
can be adjusted by turning the adjust screw 

clockwise 

to increase pressure and counterclockwise to 
decrease
 pressure.

6

Summary of Contents for ZV200

Page 1: ...rained and qualified personnel 3 Maintenance use and installation of Corken products must comply with Corken instructions applicable laws and safety standards such as NFPAPamphlet 58 for LP Gas andANS...

Page 2: ...mited warranty and the purchaser must look to the original manufacturer s warranty if any This limited warranty is void if the CORKEN product has been altered or repaired without the consent of CORKEN...

Page 3: ...VE 5 INSTALLATION OF THE ZV200 EXTERNAL AUTOMATIC BYPASS VALVE 5 Operation of the ZV200 External Automatic Bypass Valve 5 APPENDICES A Model Number Identification Code and Available Options 8 B Specif...

Page 4: ...erformance of the valve Sound Levels These products are reactionary devices used in pumping systems Sound levels are highly dependent upon the application product being pumped and installation When op...

Page 5: ...in this manual Cold Temperature Operation Impact strength is reduced at temperatures below 20 F 28 9 C Use extreme caution when working on the external bypass valve and prevent tools and other objects...

Page 6: ...tion Keeping the manual or hand operated bypass valve closed ensures the external automatic bypass valve operates in a normal capacity 2 Annual inspection and testing of the internal relief valve if a...

Page 7: ...stallations follow the guidelines provided by Underwriter s Laboratories Inc and NFPA Pamphlet 58 Notice 1 If the external automatic bypass valve is sized and set correctly a manual or hand operated b...

Page 8: ...1 Charge option D Inlet Flanges 1 25 NPT No charge option A 1 50 NPT No charge option C 2 00 NPT Standard E 2 50 NPT No charge option J 1 25 Slip on weld Charge option B 1 50 Slip on weld Charge optio...

Page 9: ...t Standard Material Optional Material Adjustment nut cap ASTM A536 65 45 12 Adjusting screw Steel Valve body Ductile iron ASTM 536 60 40 18 Valve cap Ductile iron ASTM 536 60 40 18 Gasket 1010 hot rol...

Page 10: ...ine Dimensions for Model ZV200 8 52 21 60 2 38 6 00 2 75 6 99 1 04 2 63 1 04 2 63 5 16 13 09 4 06 10 32 Discharge 2 NPT Inlet 2 NPT 1 4 pipe plug Flush plug 1 16 x 27 NPT All dimensions are in inches...

Page 11: ...10 5509 Relief valve 2 1 5511 Valve spring 91 125 psi 1 Ref No Part No Description Qty 11 7001 050NC175A Hex head bolt 8 12 5363 1 25 Flange 1 25 NPT 2 5363 1 5 Flange 1 5 NPT 2 5363 2 Flange 2 NPT 2...

Page 12: ...move any desiccant packets 5 Refer to pages 5 7 Problem Cause Solution Low capacity Valve set too low Note After all potential causes from the pump and system have been investigated Adjust valve as de...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...INC A Unit of IDEX Corporation 9201 North I 35 Service Road Oklahoma City OK 73131 Phone 405 946 5576 Fax 405 948 7343 Visit our website at http www corken com or e mail us at cocsalesdept idexcorp co...

Reviews: