background image

11

NO  C   NC   I   OC OL   Y   R    G   B

20-MINUTE 

PUSH-BUTTON SWITCHES 

(5 MAXIMUM)

A11214

Fig. 24 - Electrical connection to 20- minute lighted push button timer(s)

NOTE

: If an optional auxiliary control is activated and then, the

Dehumidistat (or Humidity Control) is being activated, the
Dehumidistat (or Humidity Control) will override the auxiliary
control commands.
Once the control(s) connections have been made, insert the

terminal connector on the recessed side of electrical compartment.
See Fig. 25.

Bottom of the unit

Terminal 
connector

A11219

Fig. 25 - Terminal connector

NOTE

: For information about the operation of the wall controls,

refer to the user guide.

ELECTRICAL CONNECTION TO THE

FURNACE

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury

or death.
Never connect a 120- volt AC circuit to the terminals of the

furnace interlock (standard wiring). Only use the low voltage

class 2 circuit of the furnace blower control

!

WARNING

For a furnace connected to a cooling system:
On some older thermostats, energizing the “R” and “G” terminals

at the furnace has the effect of energizing “Y” at the thermostat and

thereby turning on the cooling system. If you identify this type of
thermostat, you must use the ALTERNATE FURNACE

INTERLOCK WIRING. See Fig. 26.

W R G

Y

W

R

G

C

Y

UNIT TERMINAL CONNECTOR

THERMOSTAT

TERMINALS

FOUR 
WIRES

TWO WIRES

heating only

FURNACE

24-VOLT

TERMINAL BLOCK

TWO WIRES

COOLING SYSTEM

N

O

  C  

 N

C

   I   O

C

 OL   Y   R    G   B

W

R

G

Y

W

R

Y

R

G

Y

C

THERMOSTAT

TERMINAL

4 WIRES

2 WIRES

heating only

wiring
 nuts

FURNACE

24-VOLT

TERMINAL BLOCK

2 WIRES

COOLING SYSTEM

NO

NC

C

UNIT TERMINAL CONNECTOR

N

O

  C   

N

C

   I   OC 

O

L   Y   R    G   B

Standard furnace interlock wiring

Alternate furnace interlock wiring

A11215

Fig. 26 - Electrical connection to furnace

Summary of Contents for HRVCRSVU1157

Page 1: ...s be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards whic...

Page 2: ...and or certification requirements the aforementioned requirements prevail on those of this doc ument and the installer agrees to conform to these at his own expenses WARNING EQUIPMENT DAMAGE HAZARD F...

Page 3: ...les Minutes Extended Defrost Cycles Minutes _F _C Defrosting Operation Between Each Defrost Cycle Defrosting Operation Between Each Defrost Cycle 23 5 7 25 9 23 14 10 7 25 9 23 17 27 10 22 10 22 In a...

Page 4: ...blower runs when the unit is in operation but it is recommended NOTE Home with multiple forced air systems should have one unit on each system A11194 Fig 5 Central Draw Point Simplified Installation...

Page 5: ...culation applies to metric units A Example of calculation Problem The installation requires two exhaust registers one for the kitchen and the other for the bathroom The registers are connected to a ma...

Page 6: ...fresh air distribution registers in bedrooms dining rooms living room and basement S Keep in mind that the fresh air registers must be located as far as possible from the stale air registers S Install...

Page 7: ...ure to follow this caution may result in property damage When performing duct connections to the furnace supply duct this duct must be sized to support the additional airflow produced by the unit Also...

Page 8: ...r barrier shaded part in Fig 15 over the outer ring to cover it completely Fasten in place the vapor barrier using the port strap included in unit parts bag To do so insert one collar pin through vapo...

Page 9: ...e sure this loop is located OVER the T as shown Run the tube to the floor drain or to an alternative drain pipe or pail IMPORTANT If using a pail to collect water locate the tube end approximately 1 i...

Page 10: ...control ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death Always disconnect the unit before making any connections Failure in disconnecting power coul...

Page 11: ...Never connect a 120 volt AC circuit to the terminals of the furnace interlock standard wiring Only use the low voltage class 2 circuit of the furnace blower control WARNING For a furnace connected to...

Page 12: ...4 5 J14 6 J14 7 J14 8 J14 9 J14 10 Override switch optional see notes 3 4 Field wiring remote control see notes 3 4 ICP B Y R G B W BL R G B BL BN BN B B B B B BL Exhaust fan motor capacitor Supply fa...

Page 13: ...g 10 minutes after plugging the unit in you are assured that the unit is not in a defrost cycle 2 Place the magnehelic gauge on a level surface and adjust it to zero 3 Connect tubing from gauge to EXH...

Page 14: ...1 18221 4 Motor Assembly 2 18197 5 Balancing Tool 2 18220 6 Defrost Damper 1 18200 7 Damper System Assembly including Item 6 1 18199 8 Core Filter 2 18204 9 Heat Recovery Core 1 18203 10 Door Assembl...

Page 15: ...wires may be in reverse position Ensure that the color coded wires have been connected to their appropriate places The Dehumidistat or Humidity con trol or push button may be defective Jump the OL an...

Page 16: ...anada and the US EPA They meet ENERGY STAR requirements only when used in Canada 2018 CAC BDP D 7310 W Morris St D Indianapolis IN 46231 Edition Date 05 18 Manufacturer reserves the right to change at...

Reviews: