Condensing Unit Controller EC2-5X1 

2.2 

EC2-511 Condensing Unit Controller 

Copeland EazyCool™ condensing units with 2 compressors are equipped with an EC2-
511 electronic Controller modulating compressors and fans in commercial refrigeration 
applications.  
In fact there are two controllers present in the EC2-511 condensing unit controller: 

 

1 (one) for controlling compressor capacity and, 

 

1 (one) for controlling condenser pressure. 

The control target of the 

compressor controller

 is to maintain the suction pressure at a 

defined value by varying the available compressor capacity based on the “ON/OFF” of the 
compressors (EC2-511 controller). 

The control target for the 

condenser controller

 is to maintain the condensing pressure at 

a defined value by switching fans on/off on the Standard version (Two-compressor unit 
without fan speed controller - EC2-511 Controller) 

For the 

measurement

 of the 

suction pressure

 and the 

condensing pressure

, two Alco 

Controls PT4 pressure sensors with 4~20 mA interfaces are connected to the condensing 
unit controller. 

The controller has: 

 

Four relay outputs; 2 for compressor control and 2 for fan control 

 

Three digital inputs for Volt-free input contacts are available 

two of these are used for compressor serial alarm 

the third - available for a fan serial alarm - is provided with a link, which 
should be removed, for use with an external serial alarm loop. 

 
The 

display

 can show values with a decimal point in the range between -19.9 and +19.9 

otherwise without decimal point. 

 
An IR receiver for the optional IR remote control unit is built-in. 
For communication purposes, an Echelon LONWorks® interface is provided (TP/FT-10 
transceiver type). 
The supply voltage is 24 V AC. A transformer for 230V main supply to 24 V AC is fitted in 
the Copeland EazyCool™ condensing unit electrical panel. 

English 

French 

German 

 

 

 

 

 

C6.1.3/0505-0705/E 

Part no: 3125495 

Summary of Contents for EazyCool EC2-5X1

Page 1: ...Copeland EazyCoolTM outdoor condensing units Application Guidelines Controller EC2 5X1...

Page 2: ...GURATION 8 4 2 PARAMETER MODIFICATION 8 4 3 SPECIAL FUNCTIONS 8 5 Indications on the Display 9 5 1 CONTROLLER 1 9 5 2 CONTROLLER 2 9 5 3 OTHER DISPLAY INDICATIONS 9 6 List of Parameters 9 6 1 CONTROLL...

Page 3: ...ith a danger of explosion CAUTION This Icon indicates instructions to avoid property damage without or with low personnel injuries IMPORTANT This icon indicates instructions to avoid malfunction of th...

Page 4: ...driver is installed available as a factory fitted option 2 1 EC2 5X1 Nomenclature Max 2 compressor with on off modulation Max 2 condenser fans with on off modulation Max 2 compressors with on off modu...

Page 5: ...roller EC2 511 Controller For the measurement of the suction pressure and the condensing pressure two Alco Controls PT4 pressure sensors with 4 20 mA interfaces are connected to the condensing unit co...

Page 6: ...are two controllers present in the EC2 551 controller one for controlling the compressor capacity and one for controlling the condenser pressure The control target of the compressor controller is to...

Page 7: ...on pressure the condensing pressure and the saturation temperature from condensing pressure To scroll through all possible displayable data press the SEL button The display will show for one second th...

Page 8: ...om the beginning press or to show to modify another parameter etc To exit modifying the parameters with the new values Press PRG to confirm the new values and exit the parameter modification procedure...

Page 9: ...ntroller 2 parameter 5 3 Other display indications Pressure Pressure value in bar g Alarm Alarm condition IR IR communication enabled Service Transmission of Neuron ID indicator NOTE Concerning the in...

Page 10: ...e around 2 bar in medium temperature and should be reset to around 0 4 bar for low temperature Dead band should be proportional to the pressure set point i e P0 0 4 P1 0 2 or P0 2 P1 1 3 This is a thr...

Page 11: ...Hr 0 0 99 10k Hr 0 EC2 511 EC2 551 EC2 511 EC2 551 1 Value shown in display is 10 times lower 2 These values have a resolution of 10 000 hours on the local display Example value 1 means 10 000 hours...

Page 12: ...act as modulating PWM control for Copeland Digital Scroll compressor only not in use for EC2 511 c5 Compressor switch logic 0 FILO logic FILO First In Last Out Capacity demand adds first compressor ou...

Page 13: ...0 r3 Refrigerant type 0 5 4 0 5 4 EC2 511 EC2 551 r0 r1 parameters setting value depends of the refrigerant choice r3 r3 is set as default for R404A r3 Refrigerant 0 no temperature conversion 1 R22 2...

Page 14: ...Sequence Unload Sequence Modulation parameter PWM Cycle Modulation cycle F2 20 4 sec F3 100 16 sec 20 0 4 10 20 0 4 10 PWM Cycle in sec Load Sequence Unload Sequence 20 F6 The Pulse Width Modulated si...

Page 15: ...re 9 9 50 0 bar g 9 9 EC2 511 EC2 551 P0 Set point for fan modulation P1 Dead band default setting point is 4 bar Parameter t Time Parameters Min Max Unit Def Min Max Unit Def t1 1 Time delay before a...

Page 16: ...Min Max Unit Def Min Max Unit Def r0 Condensing pressure sensor min value 1 0 50 0 bar 0 0 1 0 50 0 bar 0 0 r1 Condensing pressure sensor max value 1 0 50 0 bar 30 0 1 0 50 0 bar 30 0 r2 Pressure off...

Page 17: ...e load compressor 2 compressor 1 act as modulating PWM control for Copeland Digital Scroll compressor only NOTE c4 parameter should be either 0 or 1 6 3 2 EC2 551 for Copeland EazyCool condensing unit...

Page 18: ...tual pressure value of the system Controller 1 suction pressure higher than the maximum limit A3 inactive by default Controller 2 condensing pressure higher than the maximum limit A3 Alarm during the...

Page 19: ...c6 numbers of compressors Controller 2 runs with c6 numbers of fans cE Communication error Controller 1 Communication error if binding for paralleling is used A slave controller then goes to emergency...

Page 20: ...e service button will be pressed or a 30 min delay timer will expire or a second wink request NEURON ID oF Offline The node is offline no application is running This is the result of a network managem...

Page 21: ...o 2 Pressure sensor 2 x 4 20 mA 2 wires Outputs 2 x Relays SPDT Imax 8A res 2A V AC max 250V Compressor relays 1 to 2 1 x Triac for 24 V AC Solenoid 1 x 0 10V Analog output Environmental pollution non...

Page 22: ...3 Warszawa Tel 49 0 6109 6059 0 Tel 48 225 458 9205 Fax 49 0 6109 6059 40 Fax 48 225 458 9255 France Greece Maghreb Russia CIS 8 Allee Du Moulin Berger Letnikovskaya 10 building 2 5th floor F 69130 Ec...

Reviews: