45
S225-10-30
!
SAFETY
FOR LIFE
Nominal
Test
Overall
Regulator
Single
Ratio-Adjusting Data
Terminal Potential
Voltage
Phase
Voltage
Ratio
Rating
Voltage
Internal
PT
RCT
**
**
Tap*
Ratio
Tap
2
3
4
5
6
7
2500
2500
-
20:1
120 125
20:1
2400
-
20:1
120 120
20:1
5000
5000 E
1
/P
1
40:1
120 125
40:1
4800 E
1
/P
1
40:1
120 120
40:1
4160 E
1
/P
1
40:1
104 120
34.7:1
2400 E
2
/P
2
20:1
120 120
20:1
8000 E
1
/P
1
60:1
133 120.5
66.5:1
7970 E
1
/P
1
60:1
133 120
66.5:1
7620 E
1
/P
1
60:1
127 120
63.5:1
7620
7200 E
1
/P
1
60:1
120 120
60:1
6930 E
1
/P
1
60:1
115 120.5
57.5:1
4800 E
2
/P
2
40:1
120 120
40:1
4160 E
2
/P
2
40:1
104 120
34.7:1
2400 E
3
/P
3
20:1
120 120
20:1
13800 E
1
/P
1
115:1
120 120
115:1
13200 E
1
/P
1
115:1
115 120
110.2:1
13800 12470 E
1
/P
1
115:1
104 120
99.7:1
12000 E
1
/P
1
115:1
104 120
99.7:1
7970 E
2
/P
2
57.5:1
133 120
63.7:1
7620 E
2
/P
2
57.5:1
133 120
63.7:1
7200 E
2
/P
2
57.5:1
120 120
57.5:1
6930 E
2
/P
2
57.5:1
120 120
57.5:1
14400 14400 E
1
/P
1
120:1
120 120
120:1
13800 E
1
/P
1
120:1
115 120
115:1
13200 E
1
/P
1
120:1
110 120
110:1
12000 E
1
/P
1
120:1
104 115.5
104:1
7970 E
2
/P
2
60:1
133 120
65.5:1
7620 E
2
/P
2
60:1
127 120
63.5:1
7200 E
2
/P
2
60:1
120 120
60:1
6930 E
2
/P
2
60:1
150 120.5
57.5:1
19920 19920 E
1
/P
1
166:1
120 120
166:1
17200 E
1
/P
1
166:1
104 119.5 143.9:1
16000 E
2
/P
2
120:1
133 120.5
133:1
15242 E
2
/P
2
120:1
127 120
127:1
14400 E
2
/P
2
120:1
120 120
120:1
7970 E
3
/P
3
60:1
133 120
65.5:1
7620 E
3
/P
3
60:1
127 120
63.5:1
7200 E
3
/P
3
60:1
120 120
60:1
34500 34500 E
1
/P
1
287.5:1
120 120
287.5:1
19920 E
2
/P
2
165.5:1
120 120.5 165.5:1
TAbLE 10
VR-32 Tap Connections and Voltage Levels (60 Hz)
Nominal
Test
Overall
Regulator
Single
Ratio-Adjusting Data
Terminal Potential
Voltage
Phase
Voltage
Ratio
Rating
Voltage
Internal
PT
RCT
**
**
Tap*
Ratio
Tap
2
3
4
5
6
7
6600
6930
-
54.9:1
127 119.2
58.1:1
6600
-
54.9:1
120 120.1
54.9:1
6350
-
54.9:1
115 120.6
52.6:1
6000
-
54.9:1
110 119.2
50.4:1
5500
-
54.9:1
104 115.5
47.6:1
11000 11600 E
1
/P
1
91.6:1
127 119.7
96.9:1
11000 E
1
/P
1
91.6:1
120 120.1
91.6:1
10000 E
1
/P
1
91.6:1
110 119.1
84.0:1
6930 E
2
/P
2
55.0:1
127 119.1
58.2:1
6600 E
2
/P
2
55.0:1
120 120.1
55.0:1
6350 E
2
/P
2
55.0:1
115 120.6
52.7:1
6000 E
2
/P
2
55.0:1
110 119.1
50.4:1
5500 E
2
/P
2
55.0:1
104 115.5
47.6:1
15000 15000 E
1
/P
1
120:1
120 125.0 120.0:1
14400 E
1
/P
1
120:1
120 120.0 120.0:1
13800 E
1
/P
1
120:1
115 120.0 115.0:1
13200 E
1
/P
1
120:1
110 120.0 110.0:1
12000 E
1
/P
1
120:1
104 115.4 104.0:1
11000 E
2
/P
2
91.8:1
120 119.9
91.8:1
10000 E
2
/P
2
91.8:1
110 118.9
84.1:1
6600 E
3
/P
3
53.8:1
120 122.7
53.8:1
22000 23000 E
1
/P
1
183.4:1
120 125.4 183.4:1
22000 E
1
/P
1
183.4:1
120 120.0 183.4:1
20000 E
1
/P
1
183.4:1
110 119.0 168.1:1
19100 E
1
/P
1
183.4:1
104 120.2 158.9:1
15000 E
2
/P
2
122.3:1
120 122.7 122.3:1
12700 E
2
/P
2
122.3:1
104 119.9 106.0:1
11000 E
3
/P
3
91.7:1
120 120.0
91.7:1
10000 E
3
/P
3
91.7:1
110 119.0
84.0:1
33000 34500 E
1
/P
1
275.0:1
127 115.1 291.0:1
33000 E
1
/P
1
275.0:1
120 120.0 275.0:1
30000 E
1
/P
1
275.0:1
110 119.0 252.1:1
22000 E
2
/P
2
183.3:1
120 120.0 183.3:1
20000 E
2
/P
2
183.3:1
110 119.0 168.1:1
11600 E
3
/P
3
91.7:1
127 119.0
97.0:1
11000 E
3
/P
3
91.7:1
120 120.0
91.7:1
10000 E
3
/P
3
91.7:1
110 119.0
84.0:1
* P taps are used with E taps only on regulators where an internal
potential transformer is used in conjunction with the control winding to
provide voltage supplies to the control. See nameplate for verification of
this type of control supply.
** Test terminal voltage and overall potential ratio may vary slightly from
one regulator to another. See the regulator nameplate for determining
the exact values.
TAbLE 11
VR-32 Tap Connections and Voltage Levels (50 Hz)
APPENdIx