Cooper MENVIER MF200 Manual Download Page 8

General
All cables entering the panel must be via the cable entries provided or the aperture in the rear face.
All cables must be tested for earth fault before connecting to the panel. Do not use a High Voltage
Tester (Megger) on any cable after connection to any equipment including the panel.

The wiring of each zone, interface control or alarm line should be in a 2 core cable.
The total cable resistance for each zone must not exceed 85ohm.
Any voltage drop on alarm line cables will affect the sound level of alarm devices and should be kept
to a minimum.
The Cable used for alarm devices must be of a type suitable for protection against fire for at least 30
minutes. The Extra Low voltage unscreened cables must be segregated from the mains cables.
Please refer to BS 5839 part 1 1988 for more details.

For zones and alarms the end of line resistor must be fitted to the end of the circuit. No 'spurs' shall
be used.
If a zone is not to be used the end of line resistor should be fitted in the corresponding zone terminal
block between '+' and '-'.
A cable screen termination for each panel interface is provided. The cable screen of any zone,
interface control or alarm line should be connected directly to the corresponding terminal marked 'E'.

Additional Notes On Installation For Electromagnetic Compatibility (EMC)
When used as intended  this product complies with EMC Directive (89/336/EEC) and the UK EMC
regulations 1992  (SI 2372/1992) by meeting the limits set by the standards EN61000-3-2 1994,
EN50081-1 1992 and EN50130-4 1996. The following  installation guidelines must be followed:
1.  External cables must be connected using the cable entries or knockouts provided. 
2. When routing external cables inside the product they must be

a) kept as short as possible.  
b) routed close to the metal back box.  
c) kept as far as possible from the electronics. 

Any modifications other than those in the main installation leaflet, or any other use of the product may
cause interference & is the responsibility of the user, who should ensure compliance with the EMC &
low Voltage directives.

PAGE 8

INSTALLATION INSTRUCTIONS

FAULT RELAY

REM SIG RELAY

254mm

249

Battery

Mains cable entry

Battery
connections

Printed circuit
board (PCB)

MAR424  Auxiliary
relay (PCB)

Cable entries and
blanking plugs

Mains cable entry

Mounting holes

Mounting hole

Safety isolating
Transformer

Mains terminal
block and fuse
(2A BS 1362)

Summary of Contents for MENVIER MF200

Page 1: ...NAL DI SABLE POW ER FI RE FAULT FAULT SUPERVI SOR MODE SI LENCE SOUND LAMP T EST EXI T SI LENCE BUZZE R RESET SELECT SUPERVI SOR DI SABLE TEST MF400 Cooper Lighting and Security Ltd Wheatley Hall Road...

Page 2: ...MPATIBILITY EMC 8 INSTALLING THE PANEL 9 ROUTINE TESTING 9 FAULTS 10 FUSES 10 TECHNICAL SPECIFICATION 11 FIRE ALARM SYSTEM LOG MASTER SHEET 12 THIS SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH THE REQ...

Page 3: ...e Disable Mode and Test Mode 2 Code Entry Silence Re Sound Alarms Select Function Disable or Test 3 Code Entry Lamp Test Exit Toggle through Functions Disable or Test 4 NONE RESET RESET PAGE 3 PANEL C...

Page 4: ...fire condition Note Operating RESET will not clear disable information Lamp Test Exit supervisor Mode key 3 While the supervisor LED is flashing the user can perform a lamp and buzzer test All LED s w...

Page 5: ...gh LED s representing each zone 3 When you highlight the LED corresponding to the zone to be put into Test taken out of Test press SELECT key 2 to select that zone Zone LED lit Test LED flashing 4 Eac...

Page 6: ...t present and de activates when the panel detects a fault It operates by providing 24Vdc which can be connected directly to a 24V auxiliary device e g relay and a pull down switch to 0V It is current...

Page 7: ...MAR724 MAR424 24V 10mA 24V 10mA PULL TO 0v DOOR RELEASE UNITS ETC RELAY OUTPUTS 240V 10A Resistive RELAY OUTPUTS 24V 1A Resistive NC C NO NO C NC C NC NO E E C NC NO 24V 10mA COIL MAR 724 MAR 424 24V...

Page 8: ...ce is provided The cable screen of any zone interface control or alarm line should be connected directly to the corresponding terminal marked E Additional Notes On Installation For Electromagnetic Com...

Page 9: ...is lit and the buzzer is on continuously remove the battery connection and follow step 6 again 8 Connect the front cover to the panel by locating the bottom clips in their slots and fixing the anti t...

Page 10: ...lst in the Supervisor Mode will clear this fault Indication Alarm Fault LED Flashing This fault should be investigated immediately as it should be assumed the alarms are not operational Each alarm lin...

Page 11: ...t Any Earth connection to low voltage system System Fault Micro contoller fault End of Line Elements Zones 22kohm Alarms 22kohm Maximum No of detectors per zone 20 24V 30 A each Maximum Alarm Load 750...

Page 12: ...recommended that this book is maintained by a responsible executive and that every event affecting the installation should be recorded An event should include false alarms failures tests temporary dis...

Reviews: